Relationship between Residual Charge Signals and AC Breakdown Voltages of Removed 6.6 kV XLPE Cables Using Residual Charge Detection Method with Pulse Voltages

被引:0
|
作者
Kurihara, Takashi
Okamoto, Tatsuki
Miyajima, Kazuhisa
Uchida, Katsumi
Kim, Myong Hwan
Hozumi, Naohiro
机构
关键词
XLPE cable; water tree; degradation diagnostic method; residual charge method; pulse voltage;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The residual charge method is a main diagnostic method for water tree degradation of cross-linked polyethylene (XLPE) cables in Japan. The authors have been developing a new method for diagnosis of water tree degradation of XLPE cables by using pulse voltages for charge accumulation and depolarization. In this study, we first applied pulse voltages with a pulse width of about 1 ms to removed 6.6 kV XLPE cables that had water tree degradation, and confirmed that residual charges were successfully detected in the removed cables. Then, we investigate the relationship between the residual charge signals and the AC breakdown voltages of the removed 6.6 kV XLPE cables. The results clarified that the removed cables with larger residual charge and longer duration of current signal related to water tree degradation had a lower AC breakdown voltage.
引用
收藏
页码:257 / 260
页数:4
相关论文
共 5 条
  • [1] Evaluation of Relationship between Residual Charge Signal and AC Breakdown Strength of Removed XLPE Cables at 22,66 and 77 kV Classes by Detecting Residual Charge due to Water Tree Degradation with Pulse Voltages
    Kurihara, Takashi
    Okamoto, Tatsuki
    Miyajima, Kazuhisa
    Uchida, Katsumi
    Hozumi, Naohiro
    [J]. 2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 98 - 101
  • [2] Measurement of Residual Charge using Pulse Voltages for Water Tree Degraded XLPE Cables Diagnosis
    Kurihara, Takashi
    Okamoto, Tatsuki
    Kim, Myong Hwan
    Hozumi, Naohiro
    Tsuji, Taizo
    Uchida, Katsumi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (01) : 321 - 330
  • [3] Fundamental Study on Residual Charge Detection with Pulse Voltages as Diagnostic Method of Water Tree-Degraded XLPE Cables
    Kurihara, Takashi
    Okamoto, Tatsuki
    Tsuji, Taizo
    Uchida, Katsumi
    Kim, Myong Hwan
    Hozumi, Naohiro
    [J]. PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 84 - 87
  • [4] Evaluation of Relationship between Residual Charge Signal and AC Breakdown Strength of Water-tree Degraded 22 to 77 kV Classes XLPE Cables Removed from Service using
    Kurihara, Takashi
    Okamoto, Tatsuki
    Hozumi, Naohiro
    Miyajima, Kazuhisa
    Uchida, Katsumi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) : 656 - 665