Causes and solutions of a group split of resistance-capacitance absorber for parallel reactor

被引:0
|
作者
Li, Suya [1 ]
Zhang, Chi [1 ]
Li, Lin [1 ]
Dong, Yanwei [1 ]
Sun, Zhao [1 ]
机构
[1] State Grid Tianjin Elect Power Res Inst, Tianjin, Peoples R China
关键词
D O I
10.1088/1755-1315/615/1/012059
中图分类号
S2 [农业工程];
学科分类号
0828 ;
摘要
The resistance-capacitance absorber is used in conjunction with the shunt reactor and is an important power grid equipment used to absorb the intercepted over-voltage generated during the switching process of the vacuum circuit breaker. However, the quality of the RC absorber itself affects the normal operation of the system to a certain extent.In this paper, group-cracking and oil-spilling fault of RC absorber in a 220kV transformer substation is on-site inspection, comparison test and disintegration. On this basis, solutions have been proposed, which have a certain significance to solve the group-cracking and oil-spilling fault of RC absorber.