Suppression effectiveness of water-mist sprays on accelerated wood-crib fires

被引:35
|
作者
Santangelo, Paolo E. [1 ]
Jacobs, Bryson C. [1 ]
Ren, Ning [1 ]
Sheffel, Joshua A. [2 ]
Corn, May L. [2 ]
Marshall, Andre W. [1 ]
机构
[1] Univ Maryland, Dept Fire Protect Engn, College Pk, MD 20742 USA
[2] United Technol Res Ctr, E Hartford, CT 06108 USA
关键词
Water mist; Wood crib; Suppression; Volume flux; Momentum; Surface cooling; EXTINGUISHMENT; SYSTEMS;
D O I
10.1016/j.firesaf.2014.08.012
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
An experimental analysis was conducted to quantify the water-mist discharge characteristics required to suppress wood-crib fires. The overall aim of this research was to investigate the effectiveness of these innovative systems in a canonical fire scenario. To this end, an experimental suppression facility was constructed including commercially available water mist nozzles, thermocouples for measuring the thermal transient in and around the wood cribs and a load cell for measuring the mass loss rate and the final wood crib damage. 510 x 510 x 380 mm wood cribs were used as the fuel source in all the experiments. The injection pressure and orifice diameter of the water-mist nozzles were varied in the experiments to modify the applied water flux and the initial spray momentum. These quantities were identified to be the governing parameters for suppression performance. They were characterized for all experiments along with the drop-size and velocity distributions. Critical values were determined for these quantities from first order kinematic and thermal analysis based on spray and fire source characteristics. The experimental results demonstrated critical suppression behavior consistent with this first order analysis. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:98 / 111
页数:14
相关论文
共 48 条
  • [1] FIRE SUPPRESSION BY WATER-MIST SPRAYS: EXPERIMENTAL AND NUMERICAL ANALYSIS
    Santangelo, Paolo E.
    Tartarini, Paolo
    Pulvirenti, Beatrice
    Valdiserri, Paolo
    Marshall, Andre W.
    PROCEEDINGS OF THE ASME INTERNATIONAL HEAT TRANSFER CONFERENCE - 2010, VOL 5: FUEL CELLS, GAS TURBINES, HEAT PIPES, JET IMPINGEMENT, RADIATION, 2010, : 571 - 580
  • [2] A numerical study of water-mist suppression of large scale compartment fires
    Prasad, K
    Patnaik, G
    Kailasanath, K
    FIRE SAFETY JOURNAL, 2002, 37 (06) : 569 - 589
  • [3] An experimental study on the suppression of shielded fires by water mist sprays in a compartment
    Moinuddin, Khalid
    Mahmud, H. M. Iqbal
    Joseph, Paul
    Gamble, Grant
    Suendermann, Brigitta
    Wilkinson, Cameron
    Bossard, James
    FIRE SAFETY JOURNAL, 2025, 152
  • [4] Full-Scale Experiments of Water-Mist Systems for Control and Suppression of Sauna Fires
    Santangelo, Paolo E. E.
    Tarozzi, Luca
    Tartarini, Paolo
    FIRE-SWITZERLAND, 2022, 5 (06):
  • [5] APPLICATION OF WATER SPRAYS TO EXTINGUISHMENT OF CRIB FIRES
    TAMANINI, F
    COMBUSTION SCIENCE AND TECHNOLOGY, 1976, 14 (1-3) : 17 - 23
  • [6] Experimental Study on Wood Crib Fire Suppression of Water Mist with additives
    Cui Yongyi
    Qu Fang
    Cui, Fanlin
    Jun, Zhang
    2013 FOURTH INTERNATIONAL CONFERENCE ON INTELLIGENT SYSTEMS DESIGN AND ENGINEERING APPLICATIONS, 2013, : 305 - 308
  • [7] Experiments on wood crib fire suppression with water mist in a confined space
    Liu, JH
    Huang, X
    Liao, GX
    Li, P
    PROGRESS IN SAFETY SCIENCE AND TECHNOLOGY, VOL 4, PTS A and B, 2004, 4 : 1147 - 1152
  • [8] SIMULTANEOUS APPLICATION OF BROMOFLUOROPROPENE AND WATER MIST FOR SUPPRESSING WOOD CRIB FIRES IN A CONFINED SPACE
    Zhang, Shaogang
    Ni, Xiaomin
    Zhao, Mei
    Zhang, Ruifang
    Wang, Xishi
    ATOMIZATION AND SPRAYS, 2017, 27 (05) : 465 - 476
  • [9] Overview on water-mist fire suppression system
    Yao, B.
    Chow, W.K.
    2001, American Society of Civil Engineers (07)
  • [10] Droplet evaporation with reference to the effectiveness of water-mist cooling
    Barrow, H.
    Pope, C. W.
    APPLIED ENERGY, 2007, 84 (04) : 404 - 412