A Dissolved Gas Analysis Investigation of Natural Ester under Electrical Breakdown Faults

被引:1
|
作者
Zhang, C. [1 ]
Liao, J. P. [2 ]
Zhong, L. S. [1 ]
Li, H. Q. [1 ]
Chug, J. W. [2 ]
Yu, S. M. [1 ]
Zheng, Y. Y. [1 ]
Liu, X. W. [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, 28 Xianning Rd, Xian 710049, Shaanxi, Peoples R China
[2] China Southern Power Grid Co Ltd, Maintenance & Test Ctr, EHV Transmiss Co, 181 Sci Ave, Guangzhou 510405, Guangdong, Peoples R China
关键词
Electrical Breakdown Fault; Natural Ester; Mineral Oil; DGA; Oil-Pressboard Interface;
D O I
10.1109/CEIDP49254.2020.9437454
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Natural ester has been successfully put into commercial use in high voltage transformer in recent years for its advantages in fire resistance, biodegradation, etc. This paper presents experimental results of dissolved gas analysis(DGA) of natural ester under AC breakdown faults with and without oil-pressboard interface, and mineral oil were tested as comparison. The results revealed that more CO generated in natural ester than mineral oil after breakdown, and the proportion of fault gases changed when oil-pressboard interface involved. It was also found that significant amount of bubbles formed at pre-breakdown stage in case of creeping discharge on pressboard surface.
引用
收藏
页码:196 / 199
页数:4
相关论文
共 50 条
  • [1] Difference analysis of dissolved gas in natural ester insulating fluids under typical electrical and thermal faults: An experimental study
    Xing, Yadong
    Hu, Yizhuo
    Ma, Yaoxiang
    Liu, Yang
    Dong, Ming
    Xu, Yang
    [J]. HIGH VOLTAGE, 2023, 8 (06) : 1206 - 1214
  • [2] Dissolved Gas Analysis in Mineral Oil and Natural Ester Liquids from Thermal Faults
    Meira, Matias
    Verucchi, Carlos
    Alvarez, Raul
    Catalano, Leonardo
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2021, 28 (04) : 1317 - 1325
  • [3] Gases Dissolved in Natural Ester Fluids under Thermal Faults in Transformers
    Liu, Yu
    Li, Jian
    Zhang, Zhaotao
    [J]. CONFERENCE RECORD OF THE 2012 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION (ISEI), 2012, : 223 - 226
  • [4] Dissolved Gas Analysis Investigations on Ester Liquids after Breakdown
    Eberhardt, R.
    Wieser, B.
    Lick, W.
    Muhr, H. M.
    Pukel, G.
    Schwarz, R.
    Baumann, F.
    [J]. 2011 IEEE INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2011,
  • [5] Research on the Dissolved Gas Analysis of Electrical Fault Simulation of Natural Ester Insulating Oils
    Chen Cheng
    Cai Shengwei
    Chen Jiangbo
    Shao Minfeng
    Li Hui
    Yin Jin
    Guo Huihao
    [J]. 2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 467 - 472
  • [6] The Criteria of Dissolved Gas Analysis in Natural Ester Fluid
    Dongjin, Kweon
    Kyosun, Koo
    [J]. PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 901 - 904
  • [7] Dissolved Gas Behavior in Natural Ester under Corona, Surface, and Internal Discharges
    Jongvilaikasem, Korraya
    Pattanadech, Norasage
    [J]. 2020 8TH INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD 2020), 2020, : 326 - 329
  • [8] Analysis of Gas Generated in Mineral Oil, Synthetic Ester, and Natural Ester as a Consequence of Thermal Faults
    Przybylek, Piotr
    Gielniak, Jaroslaw
    [J]. IEEE ACCESS, 2019, 7 : 65040 - 65051
  • [9] Fault Gas Generation in Natural-Ester Fluid Under Localized Thermal Faults
    Wang, Zhongdong
    Yi, Xiao
    Huang, Jinping
    Hinshaw, John V.
    Noakhes, John
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2012, 28 (06) : 45 - 56
  • [10] Gas Generation in Natural Ester and Mineral Oil Under Partial Discharge and Sparking Faults
    Wang, Zhongdong
    Wang, Xin
    Yi, Xiao
    Li, Sitao
    Hinshaw, John V.
    [J]. IEEE ELECTRICAL INSULATION MAGAZINE, 2013, 29 (05) : 62 - 70