The Numerical Simulation of the Airflow Distribution and Energy Efficiency in Data Centers with Three Types of Aisle Layout

被引:7
|
作者
Ni, Jing [1 ]
Jin, Bowen [2 ,3 ]
Ning, Shanglei [4 ]
Wang, Xiaowei [1 ]
机构
[1] Beijing Inst Petrochem Technol, Dept Informat Management & Informat Syst, Beijing 102617, Peoples R China
[2] Univ Minnesota Twin Cities, Coll Liberal Arts, Minneapolis, MN 55455 USA
[3] Univ Idaho, Coll Sci, Moscow, ID 83844 USA
[4] Beijing Inst Petrochem Technol, Coll Chem Engn, Beijing Key Lab Fuels Cleaning & Adv Catalyt Emis, Beijing 102617, Peoples R China
基金
中国国家自然科学基金;
关键词
numerical simulation; CFD; data center; airflow distribution; energy efficiency; DISTRIBUTION SYSTEMS; THERMAL MANAGEMENT; PERFORMANCE;
D O I
10.3390/su11184937
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
The energy consumption of fast-growing data centers is drawing attentions from not only energy organizations and institutions all over the world, but also charity groups, such as Greenpeace, and research shows that the power consumption of air conditioning makes up a large proportion of the electricity cost in data centers. Therefore, more detailed investigations of air conditioning power consumption are warranted. Three types of airflow distributions with different aisle layouts (the open aisle, the closed cold aisle, and the closed hot aisle) were investigated with Computational Fluid Dynamics (CFD) methods in a typical data center of four rows of racks in this study. To evaluate the results of thermal and bypass phenomenon, the temperature increase index (beta) and the energy utilization index (eta(r)) were used. The simulations show that there is a better trend of the beta index and eta(r) index both closed cold aisle and closed hot aisle compared with free open aisle. Especially with high air flow rate, the beta index decreases and the eta(r) index increases considerably. Moreover, the results prove the closed aisles (both closed cold aisle and closed hot aisle) can not only significantly improve the airflow distribution, but also reduce the mixture of cold and heat flow, and therefore improve energy efficiency. In addition, it proves the design of the closed aisles can meet the increasing density of installations and our simulation method could evaluate the cooling capacity easily.
引用
收藏
页数:13
相关论文
共 50 条
  • [1] Simulation of Thermal Distribution and Airflow for Efficient Energy Consumption in a Small Data Centers
    Ni, Jing
    Jin, Bowen
    Zhang, Bo
    Wang, Xiaowei
    [J]. SUSTAINABILITY, 2017, 9 (04):
  • [2] Aisle-capping Method for Airflow Design in Data Centers
    Takahashi, Makoto
    Uekusa, Tsuneo
    Kishita, Manabu
    Kaneko, Hideki
    [J]. INTELEC 08 - 30TH INTERNATIONAL TELECOMMUNICATIONS ENERGY, VOLS 1 AND 2, 2008, : 202 - 208
  • [3] Numerical Simulation and Comparative Analysis of Different Airflow Distributions in Data Centers
    Huang, Zhilin
    Dong, Kaijun
    Sun, Qin
    Su, Lin
    Liu, Tengqing
    [J]. 10TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, ISHVAC2017, 2017, 205 : 2378 - 2385
  • [4] DCworms - A Tool for Simulation of Energy Efficiency in Data Centers
    Piatek, Wojciech
    [J]. ENERGY EFFICIENCY IN LARGE SCALE DISTRIBUTED SYSTEMS, EE-LSDS 2013, 2013, 8046 : 118 - 124
  • [5] Energy Assessment of CRAH Bypass for Enclosed Aisle Data Centers
    Erden, Hamza Salih
    Yildirim, Mehmet Turgay
    Koz, Mustafa
    Khalifa, H. Ezzat
    [J]. 2016 15TH IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM), 2016, : 433 - 439
  • [6] Numerical simulation of airflow distribution in mine tunnels
    Ding Cui
    He Xueqiu
    Nie Baisheng
    [J]. International Journal of Mining Science and Technology, 2017, 27 (04) : 663 - 667
  • [7] Numerical simulation of airflow distribution in mine tunnels
    Ding Cui
    He Xueqiu
    Nie Baisheng
    [J]. INTERNATIONAL JOURNAL OF MINING SCIENCE AND TECHNOLOGY, 2017, 27 (04) : 663 - 667
  • [8] Towards Energy Efficiency in Data Centers: An Industrial Experience Based on Reuse and Layout Changes
    Machado, Romulos da S.
    Pires, Fabiano dos S.
    Caldeira, Giovanni R.
    Giuntini, Felipe T.
    Santos, Flavia de S.
    Fonseca, Paulo R.
    [J]. APPLIED SCIENCES-BASEL, 2021, 11 (11):
  • [9] Balancing Cooling and IT Airflow with Dampers in Ceiling-Ducted Hot-Aisle Containment in Data Centers
    VanGilder, James
    Zhang, Yan
    Linder, Stephen
    Condor, Michael
    [J]. PROCEEDINGS OF THE 2019 EIGHTEENTH IEEE INTERSOCIETY CONFERENCE ON THERMAL AND THERMOMECHANICAL PHENOMENA IN ELECTRONIC SYSTEMS (ITHERM 2019), 2019, : 1282 - 1288
  • [10] Effects of airflow on the thermal environment and energy efficiency in raised-floor data centers: A review
    Jin, Chaoqiang
    Bai, Xuelian
    Yang, Chao
    [J]. SCIENCE OF THE TOTAL ENVIRONMENT, 2019, 695