NORMALIZATION OF DOUBLE-CIRCUIT OVERHEAD LINE MAGNETIC FIELD INSIDE KHRUSHCHEV BUILDING

被引:2
|
作者
Chunikhin, K., V [1 ]
Grinchenko, V. S. [1 ]
机构
[1] Natl Acad Sci Ukraine, State Inst, Inst Tech Problems Magnetism, 19 Ind Str, UA-61106 Kharkiv, Ukraine
关键词
magnetic field; overhead line; grid shield; reference level; quantity of metal; FREQUENCY;
D O I
10.20998/2074-272X.2021.3.06
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with the mitigation of 110 kV double-circuit overhead line magnetic field inside five-story Khrushchev buildings. We show that the magnetic field can exceed the reference level 0.5 mu T in 90 % part of living space. To mitigate the magnetic field, we propose the inverted L-shaped grid shield with conductors on the wall and in the attic of the building. Using the analytical model of the grid shield and the numerical simulation, we determine the parameters of the L-shaped grid shield which provides the magnetic field normalization in 97 % part of living space. Further improvement of the grid shield profile, in particular, the placement of some conductors in the basement, allows to reduce the quantity of metal of the shield by 15 % while maintaining the shielding efficiency. Also we consider the magnetic field normalization for the overhead line with a rated current of 500 A. In this case, the quantity of metal of the grid shield increases 2.74 times. References 19, table 1, figures 5.
引用
收藏
页码:38 / 41
页数:4
相关论文
共 50 条
  • [1] Mitigation of magnetic field under double-circuit overhead transmission line
    Gouda, Osama Elsayed
    El Dein, Adel Z.
    Telkomnika - Indonesian Journal of Electrical Engineering, 2012, 10 (08): : 2272 - 2284
  • [2] Zero sequence behaviour of a double-circuit overhead line
    Benato, Roberto
    Sessa, Sebastian Dambone
    Guglielmi, Fabio
    Partal, Ertugrul
    Tleis, Nasser
    ELECTRIC POWER SYSTEMS RESEARCH, 2014, 116 : 419 - 426
  • [3] Zero Sequence Behaviour of a Double-Circuit Overhead Line
    Benato, Roberto
    Sessa, Sebastian Dambone
    Guglielmi, Fabio
    Partal, Ertugrul
    Tleis, Nasser
    2014 IEEE PES T&D CONFERENCE AND EXPOSITION, 2014,
  • [4] Novel multi-objective optimization method of electric and magnetic field emissions from double-circuit overhead power line
    Rankovic, Aleksandar
    INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2017, 27 (02):
  • [5] Double Circuit 110 kV Overhead Line Magnetic Field Analysis
    Molnar-Matei, Florin
    Andea, Petru
    Pana, Adrian
    Teslovan, Razvan
    2012 16TH IEEE MEDITERRANEAN ELECTROTECHNICAL CONFERENCE (MELECON), 2012, : 780 - 783
  • [6] MAGNETIC FIELD NORMALIZATION IN RESIDENTIAL BUILDING LOCATED NEAR OVERHEAD LINE BY GRID SHIELD
    Grinchenko, V. S.
    Chunikhin, K., V
    ELECTRICAL ENGINEERING & ELECTROMECHANICS, 2020, (05) : 38 - 43
  • [7] Procedure for Verifying Population Exposure Limits to the Magnetic Field from Double-Circuit Overhead Power Lines
    Landini, Marco
    Mazzanti, Giovanni
    Mandrioli, Riccardo
    ELECTRICITY, 2021, 2 (03): : 342 - 358
  • [8] Phase current asymmetry on the double-circuit very high voltage overhead transmission line
    Nazarcik, Tomas
    Rawn, Barry
    2016 17TH INTERNATIONAL SCIENTIFIC CONFERENCE ON ELECTRIC POWER ENGINEERING (EPE), 2016, : 80 - 84
  • [9] Transmission Efficiency Optimization for the operation of double-circuit Overhead Lines
    Papazoglou, Thales M.
    ELEKTROTEHNISKI VESTNIK-ELECTROCHEMICAL REVIEW, 2011, 78 (03): : 102 - 105
  • [10] Distribution of Magnetic Field in 400 kV Double-Circuit Transmission Lines
    Deltuva, Ramunas
    Lukocius, Robertas
    APPLIED SCIENCES-BASEL, 2020, 10 (09):