HVDC Converter Transformer Saturation in Hybrid AC/DC System Caused by Coupled Transmission Lines

被引:0
|
作者
Zhang, Shuoting [1 ]
Li, Yalong [1 ]
Liu, Bo [1 ]
Shi, Xiaojie [1 ]
Tolbert, Leon M. [1 ]
Wang, Fred [1 ]
机构
[1] Univ Tennessee, Dept Elect Engn & Comp Sci, Ctr Ultrawide Area Resilient Elect Energy Transmi, Knoxville, TN 37996 USA
基金
美国国家科学基金会;
关键词
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Hybrid ac/dc transmission can increase the power transfer capability of long ac transmission lines. High voltage dc (HVDC) converters are needed, and the line-commutated converter (LCC) is used considering the dc fault current controllability. However, zero-sequence current can be generated due to the coupled transmission lines, and it will flow into the HVDC converters as a fundamental frequency current component on dc side (i(60)). The LCC will convert i(60) to dc current components on the ac side, which may cause potential converter transformer saturation. This paper analyzes the influence of coupled transmission lines on i(60) and the converter transformer saturation and proposes two possible solutions to avoid converter transformer saturation. The simulationresults verify the effectiveness of the proposed methods.
引用
收藏
页码:411 / 415
页数:5
相关论文
共 50 条
  • [1] Hybrid DC/DC Converter for HVDC Transmission System
    Li B.
    Zhang S.
    Cheng D.
    Wang W.
    Xu D.
    [J]. Li, Binbin (libinbin@hit.edu.cn), 2018, Automation of Electric Power Systems Press (42): : 116 - 122
  • [2] A New AC/DC Converter for the Interconnections between Wind Farms and HVDC Transmission Lines
    Nouri, Soheil
    Babaei, Ebrahim
    Hosseini, Seyyed Hossein
    [J]. JOURNAL OF POWER ELECTRONICS, 2014, 14 (03) : 592 - 597
  • [3] Fault Location in Hybrid AC/DC Transmission Grids Containing DERs and HVDC Lines
    Galvez, Cesar
    Abur, Ali
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 2024, 39 (01) : 329 - 340
  • [4] A Line Impedance Conditioner for Saturation Mitigation of Zigzag Transformer in Hybrid AC/DC Transmission System Considering Line Unbalances
    Liu, Bo
    Shi, Xiaojie
    Li, Yalong
    Wang, Fei
    Tolbert, Leon M.
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2017, 32 (07) : 5070 - 5086
  • [5] Protection of Permanent Faults on DC Overhead Lines in Hybrid Converter Based HVDC System
    Gijare, P. P.
    Tade, S. V.
    [J]. 2015 INTERNATIONAL CONFERENCE ON ENERGY SYSTEMS AND APPLICATIONS, 2015, : 302 - 305
  • [6] Analysis on characteristics of HVDC power transmission system in AC/DC hybrid system considering load model of AC system
    [J]. Xiao, J. (sccd1949@163.com), 1600, Power System Technology Press (37):
  • [7] HVDC 50 Hz and 100 Hz protection of AC/DC hybrid transmission system
    Technology Research Center of China Southern Power Grid, Guangzhou 510623, China
    [J]. Dianli Xitong Zidonghue, 2008, 12 (57-60+103):
  • [8] DC Components in the AC Networks Containing AC/DC Hybrid Transmission Lines
    Novitskiy, Alexander
    Westermann, Dirk
    [J]. 2016 IEEE 16TH INTERNATIONAL CONFERENCE ON ENVIRONMENT AND ELECTRICAL ENGINEERING (EEEIC), 2016,
  • [9] The hybrid transformer with a bipolar AC/AC converter without DC energy storage
    Kaniewski, Jacek
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2018, 94 (05): : 80 - 85
  • [10] A Novel Single-Terminal Fault Location Method for AC Transmission Lines in a MMC-HVDC-Based AC/DC Hybrid System
    Xue, Shimin
    Lu, Junchi
    Liu, Chong
    Sun, Yabing
    Liu, Baibing
    Gu, Cheng
    [J]. ENERGIES, 2018, 11 (08):