Studies of on-line monitoring of pressure in vacuum interrupters

被引:0
|
作者
Mao, Huiyong [1 ]
Wang, Yi [1 ]
机构
[1] Beijing Jiaotong Univ, Sch Elect Engn, Beijing 100044, Peoples R China
关键词
inverted magnetron gauge; low-power consumption; on-line monitoring; pressure measurement; pulsed discharge; vacuum interrupters;
D O I
10.1109/PSCE.2006.296194
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Some methods for on-line monitoring of pressure in vacuum interrupters were reviewed. Experiments were carried out to investigate the characteristics of an inverted magnetron vacuum gauge in pulsed discharge mode, which can measure pressures ranging from 3X10-4Pa to 0.5Pa. According to the experimental results, a kind of vacuum tube with intellectualized vacuum sensor was developed to implement the on-line monitoring of pressure in vacuum interrupters. Discharge in the vacuum sensor was performed in a pulsed mode. The vacuum sensor was powered by batteries and was able to communicate the results of measurement to other devices by radio, infrared or optical fibre.
引用
收藏
页码:1851 / +
页数:3
相关论文
共 50 条
  • [1] On-line monitoring of pressure in vacuum interrupters
    Mao, Huiyong
    Chang, Guang
    Zhu, Xuegui
    Wang, Yi
    IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2007, 14 (01) : 179 - 184
  • [2] A vacuum interrupters internal pressure on-line condition monitoring system
    Dept. of Mechanical and Electrical Engineering, Guilin University of Electronic Technology, Guilin, 541004, China
    不详
    不详
    Proc. Int. Symp. Discharge. Electr. Insul. Vac. ISDEIV, (485-488):
  • [3] A Vacuum Interrupters Internal Pressure On-line Condition Monitoring System
    Liu Xu-dong
    Fan Xing-ming
    Zhang Xin
    Zou Qi-tao
    Fan Jian-rong
    Liang Cong
    Shi Wei-jian
    25TH INTERNATIONAL SYMPOSIUM ON DISCHARGES AND ELECTRICAL INSULATION IN VACUUM (ISDEIV 2012), 2012, : 485 - 488
  • [4] Pressure Monitoring in Medium-Voltage Vacuum Interrupters
    Wegierek, Pawel
    Kostyla, Damian
    Lech, Michal
    Kozak, Czeslaw
    Zielonka, Alicja
    ENERGIES, 2023, 16 (18)
  • [5] Novel method of on-line monitoring vacuum for vacuum circuit breaker
    Zhenjiang Tailifeng Electronic Co. Ltd., Zhenjiang 212021, China
    Dianli Xitong Zidonghue, 2006, 11 (49-51+60):
  • [6] Development of on-line monitoring system for vacuum degree of vacuum switch
    Zhou, LX
    Zhou, RJ
    Li, WG
    Deng, BZ
    Li, KK
    Conference Record of the 2005 IEEE Industry Applications Conference, Vols 1-4, 2005, : 848 - 851
  • [7] Experimental study of on-line detecting vacuum pressure of vacuum interrupter
    Duan, Xiongying
    Zhao, Ziyu
    Zou, Jiyan
    Gaoya Dianqi/High Voltage Apparatus, 2000, 36 (04): : 30 - 32
  • [8] On-line monitoring of systolic pressure variation
    Fujita, Y
    Sari, A
    Yamamoto, T
    ANESTHESIA AND ANALGESIA, 2003, 96 (05): : 1529 - 1530
  • [9] Analysis on dynamic vacuum pressure in high current vacuum interrupters
    Zou, Jiyan
    Chen, Xuanshu
    Zhang, Hanmin
    Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 1996, 11 (05): : 19 - 22
  • [10] On-line monitoring of vacuum dryers using mass spectrometry
    Ende, DJA
    Preigh, MJ
    Hettenbach, K
    Ahlijanian, P
    Ward, HW
    ORGANIC PROCESS RESEARCH & DEVELOPMENT, 2000, 4 (06) : 587 - 593