Calculational method of transient electric field excited by partial discharge in gas insulated substation using dyadic green function

被引:0
|
作者
Xu, GF [1 ]
Sun, CX [1 ]
Tang, J [1 ]
Tang, Z [1 ]
Wei, Z [1 ]
机构
[1] Chongqing Univ, Minist Educ, Lab High Voltage Engn & Elect New Technol, Chongqing 400044, Peoples R China
关键词
transient electric field; dyadic Green function; partial discharge; Gas Insulated Substation;
D O I
暂无
中图分类号
TP18 [人工智能理论];
学科分类号
081104 ; 0812 ; 0835 ; 1405 ;
摘要
In this paper, Gaussian current pulse is used to simulate the PD current pulse in Gas Insulated Substation(GIS). The. expressions of transient. electric field excited by PD in GIS are deduced out by using dyadic Green function theory, which is important to study onthe principle of detecting PD in GIS using ultra high frequency (UHF) method. The calculating results of electric field show that the TEM mode and high order modes excited by PD make different contributions to the electric field. So the contributions of TEM mode and all the high order modes in the detection frequency scope should be taken into consideration when calculating the electric field excited by PD in GIS.
引用
收藏
页码:1438 / 1441
页数:4
相关论文
共 29 条
  • [1] Novel Method for Partial Discharge Detection in Gas Insulated Substation
    Wang, Chuanning
    Liu, Baowen
    Xu, Honghua
    Jin, Jiping
    Ma, Hongzhong
    [J]. 2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,
  • [2] Electric Field Modelling in Gas-Insulated Substation for Analysis of Conditions for Partial Discharge Phenomena
    Florkowska, B.
    Zydron, P.
    Jackowicz-Korczynski, A.
    [J]. ACTA PHYSICA POLONICA A, 2015, 128 (03) : 319 - 325
  • [3] Development of partial discharge monitoring technique using a neural network in a gas insulated substation
    Haida, T
    Wakabayashi, S
    Tsuge, R
    Sakakibara, T
    [J]. IEEE TRANSACTIONS ON POWER SYSTEMS, 1997, 12 (02) : 1014 - 1021
  • [4] Source classification of partial discharge for gas insulated substation using waveshape pattern recognition
    Chang, C
    Chang, CS
    Jin, J
    Hoshino, T
    Hanai, M
    Kobayashi, N
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2005, 12 (02) : 374 - 386
  • [5] Development of partial discharge monitoring technique using a neural network in a gas insulated substation
    Oki, I
    Haida, T
    Wakabayashi, S
    Tsuge, R
    Sakakibara, T
    Murase, H
    [J]. 1996 IEEE TRANSMISSION AND DISTRIBUTION CONFERENCE PROCEEDINGS, 1996, : 189 - 196
  • [6] Gas Insulated Substation Grounding System Design Using the Electromagnetic Field Method
    Liu, Jie
    Dawalibi, Farid P.
    Majerowicz, Brian F.
    [J]. 2012 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2012,
  • [7] Localization Method for Multiple Partial Discharge Sources in Air-insulated Substation by Using Plane Intersection Method
    Zhu M.
    Liu Q.
    Wang Y.
    Deng J.
    Zhang G.
    Guo A.
    [J]. Zhang, Guanjun (gjzhang@mail.xjtu.edu.cn), 2018, Science Press (44): : 2970 - 2976
  • [8] A calculation method of transient field under very fast transient over-voltage in gas insulated substation (GIS)
    Gao, YH
    Yuan, H
    Wang, EZ
    Cao, YD
    [J]. APPLIED ELECTROMAGNETICS (III), 2001, 10 : 215 - 218
  • [9] Partial Discharge Diagnosis of Gas Insulated Station (GIS) Using Acoustic Method
    Suwarno
    Caesario, P.
    Anita, P.
    [J]. 2009 INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING AND INFORMATICS, VOLS 1 AND 2, 2009, : 649 - 653
  • [10] Partial discharge and interference discrimination in gas-insulated systems using electric and magnetic sensors
    Mier, Christian
    Mor, Armando Rodrigo
    Luo, Tianming
    Vaessen, Peter
    [J]. INTERNATIONAL JOURNAL OF ELECTRICAL POWER & ENERGY SYSTEMS, 2024, 158