Line fault location for multi-terminal MMC-HVDC system based on SWT and SVD

被引:2
|
作者
Huai, Qing [1 ,2 ]
Liu, Kaipei [1 ]
Hooshyar, Ali [2 ]
Ding, Hua [3 ]
Qin, Liang [1 ]
Chen, Kun [4 ]
机构
[1] Wuhan Univ, Sch Elect Engn & Automat, Wuhan, Hubei, Peoples R China
[2] Univ Toronto, Elect & Comp Engn Dept, Toronto, ON, Canada
[3] State Grid Integrated Energy Serv Grp CO Ltd, Beijing, Peoples R China
[4] State Grid Hubei Elect Power Res Inst, Wuhan, Hubei, Peoples R China
关键词
power transmission faults; power transmission protection; fault location; singular value decomposition; HVDC power transmission; HVDC power convertors; wavelet transforms; line fault location; multiterminal MMC-HVDC system; SWT; travelling wave-based method; locating DC line faults; fault TW signals; multiterminal HVDC system; TW-based fault location principles; signal-processing techniques; remote fault; fault resistance; TW propagation velocity; TW principle; fault point; SVD result; wave heads; arrival times; TW arrivals; hankel matrix-based singular value decomposition; improved threshold functions; stationary wavelet; pole voltage signals; local information; direct current system; modular multilevel converter-based high-voltage;
D O I
10.1049/iet-rpg.2020.0702
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study presents a travelling wave (TW)-based method for locating DC line faults in a modular multilevel converter (MMC)-based high-voltage direct current (HVDC) system by using local information. Pole voltage signals are adopted and denoised via stationary wavelet transform (SWT) with improved threshold functions. Hankel matrix-based singular value decomposition (SVD) is utilised to detect TW arrivals. The arrival times of incidental and reflected wave heads are observed in SVD result. The reflected wave heads from the fault point and the opposite end can be discriminated by comparing surge polarities in SVD result. The proposed method relies on the TW principle but is independent of TW propagation velocity. The feasibility of the proposed algorithm is evaluated considering potential factors, such as fault resistance, close-in fault, remote fault, sampling rate and noise. The superiority of this method is validated by comparing it with other signal-processing techniques and TW-based fault location principles. Electromagnetic transient simulation of the multi-terminal HVDC system on Power Systems Computer Aided Design / Electromagnetic Transients including DC (PSCAD/EMTDC) is conducted to provide fault TW signals, which are analysed in MATLAB. A corresponding equivalent test model developed in a real-time digital simulator is also provided for conducting a supplementary study to verify and further research this fault location method.
引用
收藏
页码:4043 / 4052
页数:10
相关论文
共 50 条
  • [1] Fault Location Scheme for Multi-terminal MMC-HVDC System Based on VMD-SVD
    Yang, Dongfeng
    Wang, He
    Liu, Xiaojun
    Wang, Zhongyi
    [J]. Dianwang Jishu/Power System Technology, 2022, 46 (08): : 3084 - 3093
  • [2] Fault location scheme for multi-terminal MMC-HVDC system based on mathematical morphology
    Yu, Xiuyong
    Xiao, Liye
    [J]. Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2020, 40 (01): : 93 - 100
  • [3] Fault location of an MMC-HVDC line based on CRS-LMD and SVD
    He, Yuyang
    Ma, Qianli
    Yu, Fei
    Liu, Ximei
    [J]. Dianli Xitong Baohu yu Kongzhi/Power System Protection and Control, 2024, 52 (01): : 121 - 132
  • [4] A Model-Based DC Fault Location Scheme for Multi-Terminal MMC-HVDC Systems Using a Simplified Transmission Line Representation
    Xu, Jianzhong
    Lu, Yu
    Zhao, Chengyong
    Liang, Jun
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2020, 35 (01) : 386 - 395
  • [5] Fast Fault Detection Scheme for Multi-terminal MMC-HVDC Based on Novel Fault Directional Criterion
    Yu, Xiuyong
    Xiao, Liye
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (24): : 8437 - 8446
  • [6] On Systematic DC Fault-Ride-Through of Multi-terminal MMC-HVDC Grids
    Niaki, Seyed Hassan Ashrafi
    Chen, Zhe
    Bak-Jensen, Birgitte
    Sharifabadi, Kamran
    Liu, Zhou
    Hu, Shuju
    [J]. 2021 56TH INTERNATIONAL UNIVERSITIES POWER ENGINEERING CONFERENCE (UPEC 2021): POWERING NET ZERO EMISSIONS, 2021,
  • [7] Computationally Efficient Method for Simulating Multi-Terminal MMC-HVDC
    Jiang, Haihao
    Wang, Can
    Joos, Geza
    Ooi, B. T.
    [J]. 2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [8] DC Fault Current Estimation in a Multi-Terminal Hybrid MMC-HVDC System Considering Fault Ride Through Control
    Xu, Yi
    Qin, Liang
    Zhang, Yi
    Liu, Kaipei
    Blaabjerg, Frede
    [J]. 2021 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2021, : 3146 - 3153
  • [9] Two-terminal Asynchronous Fault Location Method for MMC-HVDC Transmission Line
    MMC-HVDC输电线路双端非同步故障测距方法
    [J]. Huang, Chun (yellowpure@hotmail.com), 2018, Automation of Electric Power Systems Press (42):
  • [10] A Coordinated Protection Scheme for DC Faults in Multi-terminal MMC-HVDC Transmission System
    Ma, Yanjun
    Li, Haifeng
    Wang, Gang
    Xie, Qiuxia
    [J]. PROCEEDINGS OF 2017 2ND INTERNATIONAL CONFERENCE ON POWER AND RENEWABLE ENERGY (ICPRE), 2017, : 255 - 260