A Comparative Investigation of Presaturated Core Fault Current Limiters Biased by DC Current and Permanent Magnet

被引:5
|
作者
Eladawy, Mohamed [1 ,3 ]
Metwally, Ibrahim A. [2 ,3 ]
机构
[1] Shaqra Univ, Coll Engn, Elect Engn Dept, Dawadmi 11911, Saudi Arabia
[2] Sultan Qaboos Univ, Coll Engn, Dept Elect & Comp Engn, Muscat 123, Oman
[3] Mansoura Univ, Fac Engn, Elect Engn Dept, Mansoura 35516, Egypt
关键词
Fault current limiter (FCL); finite element (FE) method; iron core; permanent magnet (PM); self-triggering; JILES-ATHERTON MODEL; SIMULATION; DESIGN;
D O I
10.1109/TMAG.2019.2926658
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this paper, the dc biasing magnetomotive force (mmf) in presaturated core fault current limiter (PCFCL) is replaced with permanent magnet (PM) to overcome the well-known drawbacks of the dc biased PCFCLs. These drawbacks are excessively induced voltage across the terminals of the dc coil during fault condition and high total power losses during the steady-state condition. The novel contributions of this paper are the introduction of the selection criteria of PM material and its representation by actual nonlinear B-H hysteresis loop of Jiles-Atherton method, and the use of PM alone as an equivalent to the dc biasing coils for three-phase fault current limiter (FCL), contrary to work reported in earlier papers. Single- and three-phase PCFCLs are modified by replacement of dc saturation coil by the equivalent PM through time-domain finite element (FE) simulation of COMSOL Multiphysics package. Experimental verification shows that the implementation of accurate nonlinear representation of PM demagnetization curve with FE simulation gives a realistic performance of the PM biased PCFCL, especially in the fault condition. The performance of PCFCL can be evaluated through the voltage drop and total power losses during the steady-state condition and the fault current clipping ratio during fault condition of the grid. Furthermore, a comparative investigation of dynamic behavior is considered between dc and PM biased PCFCLs. It is found that the PM biased PCFCL has enriched capability of limiting any type of fault current with leading advantages of reduced voltage drop and power losses significantly together with risk elimination of the high induced voltage across dc coil terminals. Moreover, the governing parameters of PM biased PCFCLs are subjected to performance analysis to study their inherent effects.
引用
收藏
页数:10
相关论文
共 50 条
  • [1] Compact designs of permanent-magnet biased fault current limiters
    Eladawy, Mohamed
    Metwally, Ibrahim A.
    IET ELECTRIC POWER APPLICATIONS, 2020, 14 (03) : 471 - 479
  • [2] Investigation of the performances of a permanent magnet biased fault current limiting reactor with a steel core
    Mukhopadhyay, SC
    Iwahara, M
    Yamada, S
    Dawson, FP
    IEEE TRANSACTIONS ON MAGNETICS, 1998, 34 (04) : 2150 - 2152
  • [3] Investigation of the Performance of A Nove Permanent Magnet Biased Fault Current Limiter
    Yuan, J.
    Lei, Y.
    Wei, L.
    Chen, B.
    2015 IEEE MAGNETICS CONFERENCE (INTERMAG), 2015,
  • [4] Presaturated iron-core fault current limiters for MVDC power system applications
    Metwally, Ibrahim A.
    Eladawy, Mohamed
    IET ELECTRIC POWER APPLICATIONS, 2024, 18 (12) : 1978 - 1990
  • [5] Transient dynamic analyses of presaturated core fault current limiters through flux and inductance versus current modelling
    Eladawy, Mohamed
    Tarhuni, Naser J.
    Metwally, Ibrahim A.
    IET ELECTRIC POWER APPLICATIONS, 2019, 13 (09) : 1263 - 1272
  • [6] Performance Investigation of a Novel Permanent Magnet-Biased Fault-Current Limiter
    Yuan, Jiaxin
    Lei, Yang
    Tian, Cuihua
    Chen, Baichao
    Yu, Zhangting
    Yuan, Jian
    Zhou, Junwei
    Yang, Kehu
    IEEE TRANSACTIONS ON MAGNETICS, 2015, 51 (11)
  • [7] Optimal Design of Parameters for High Voltage DC Fault Current Limiter with Permanent-magnet-biased Saturation
    Yuan J.
    Zhang Z.
    Zhou H.
    Gan P.
    Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2020, 44 (13): : 135 - 142
  • [9] Increasing Energy Efficiency of Saturated-Core Fault Current Limiters With Permanent Magnets
    Knott, Jonathan C.
    Moscrop, Jeffrey W.
    IEEE TRANSACTIONS ON MAGNETICS, 2013, 49 (07) : 4132 - 4136
  • [10] Dynamic core length in saturated core fault current limiters
    Nikulshin, Y.
    Wolfus, Y.
    Friedman, A.
    Yeshurun, Y.
    SUPERCONDUCTOR SCIENCE & TECHNOLOGY, 2013, 26 (09):