This paper starts with the reasons why on-site oil reclamation processing was required for two 250MVA 3-phi banks of single-phase transformers. It reviews the results of routine diagnostics and describes the application of a new off-line diagnostic tool, Polarisation / Depolarisation Current (PDC) Analysis in the verification of, the effectiveness of the oil reclamation process. The moisture in insulating paper of each unit as assessed by the new tool is reported, in addition to various insulation properties such as oil conductivity, insulation resistance, polarisation index and recovery voltage. Finally, the comparison of PDC analysis result before and after oil reclamation indicates the degree of improvement in the insulation system and the final condition of the transformers.
引用
收藏
页码:105 / 108
页数:4
相关论文
共 44 条
  • [1] Insulation condition assessment of transformer bushings by means of polarisation/depolarisation current analysis
    Bhumiwat, SA
    [J]. CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, : 500 - 503
  • [2] Multifractal Analysis on Polarisation and Depolarisation current of the Transformer Insulation
    Jadav, Raj B.
    Saha, Tapan K.
    Ekanayake, Chandima
    [J]. 2012 22ND AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC): GREEN SMART GRID SYSTEMS, 2012,
  • [3] Advanced applications of Polarisation/Depolarisation Current analysis on power transformers
    Bhumiwat, S. A.
    [J]. CONFERENCE RECORD OF THE 2008 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 2008, : 474 - 477
  • [4] Insulation diagnostics on power transformers using the polarisation and depolarisation current (PDC) analysis
    Leibfried, T
    Kachler, AJ
    [J]. CONFERENCE RECORD OF THE 2002 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2002, : 170 - 173
  • [5] On-site diagnosis of power transformers by means of relaxation current measurements
    Der Houhanessian, V
    Zaengl, WS
    [J]. CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1998, : 28 - 34
  • [6] Transformer Diagnostics Using Dissolved Gas Analysis and Polarisation and Depolarisation Current Measurements - A case study
    Jadav, Raj B.
    Saha, Tapan K.
    Ekanayake, Chandima
    [J]. 2011 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING CONFERENCE (AUPEC), 2011,
  • [7] Mobile laboratory for on-site oil analysis and maintenance
    Karl, H.
    [J]. Tribologie und Schmierungstechnik, 2001, 48 (02): : 26 - 31
  • [8] Small and Mobile: The future of on-site oil analysis
    Fematt, Josh
    [J]. TRIBOLOGY & LUBRICATION TECHNOLOGY, 2013, 69 (08) : 34 - +
  • [9] On-site data analysis of an electronic current transformer
    Zheng, Q
    Xiang, Z
    Mei, ZG
    Luo, CM
    [J]. CONFERENCE RECORD OF THE 2004 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, 2004, : 414 - 417
  • [10] A Novel Fixed Fibre Biofilm Membrane Process for On-Site Greywater Reclamation Requiring No Fouling Control
    Jabornig, Simon
    Podmirseg, Sabine Marie
    [J]. BIOTECHNOLOGY AND BIOENGINEERING, 2015, 112 (03) : 484 - 493