Feasibility study of desiccant air-conditioning system in Thailand

被引:19
|
作者
Hirunlabh, J. [1 ]
Charoenwat, R.
Khedari, J.
Teekasap, Sombat
机构
[1] King Mongkuts Univ Technol Thonburi, Bldg Sci Res Ctr, Bangkok 10140, Thailand
[2] SE Asia Univ, Engn Management Program, Bangkok 10160, Thailand
关键词
economic; energy saving; silica gel;
D O I
10.1016/j.buildenv.2005.09.022
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
The objective of this study was to conduct an experimental analysis to investigate the performance and energy saving of the well-known desiccant air-conditioning system in Thailand. The system was composed of a silica gel bed, a split type air-conditioner (1.5 ton refrigeration) installed in a room of volume 76.8 m(3), air ducts and a blower. Its design allows us to adjust the percentages of return air, outdoor air and indoor air mixed to the air leaving the desiccant, and desiccant bed thickness as well. Tests were conducted on several days with relatively similar ambient conditions. Under the test conditions used here, a 5 cm bed thickness is recommended with a maximum adsorption rate of 473 g/h. The optimum percentages of air ratios are as follows: 15% outdoor air, 15% return air (mixed together at the desiccant bed inlet) and 70% of indoor air mixed to the dry air leaving the desiccant. The corresponding electricity saving was about 24%. As expected, simple economic analysis indicated that the desiccant air-conditioning is only viable for large cooling capacities and central air-conditioned buildings. The payback period is about 4 yr. (c) 2005 Elsevier Ltd. All rights reserved.
引用
收藏
页码:572 / 577
页数:6
相关论文
共 50 条
  • [1] The desiccant air-conditioning system
    [J]. Riffat, S.B, 1600, Ambient Press Ltd (25):
  • [2] A feasibility study of a solar desiccant air-conditioning system - Part II: Transient simulation and economics
    Davanagere, BS
    Sherif, SA
    Goswami, DY
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1999, 23 (02) : 103 - 116
  • [3] Study on the Application of Rotary Desiccant Air-Conditioning System on Ships
    Chen, Wu
    Yang, Guanghai
    [J]. ADVANCED SCIENCE LETTERS, 2011, 4 (4-5) : 1410 - 1415
  • [4] Analysis on a hybrid desiccant air-conditioning system
    Jia, C. X.
    Dai, Y. J.
    Wu, J. Y.
    Wang, R. Z.
    [J]. APPLIED THERMAL ENGINEERING, 2006, 26 (17-18) : 2393 - 2400
  • [5] Study on Desiccant Air-Conditioning System for Livestock Application in Pakistan
    Niaz, Hassan
    Sultan, Muhammad
    Miyazaki, Takahiko
    Khan, Zahid M.
    [J]. 2018 2ND INTERNATIONAL CONFERENCE ON ENERGY CONSERVATION AND EFFICIENCY (ICECE), 2018, : 19 - 22
  • [6] A feasibility study of a solar desiccant air-conditioning system - Part I: Psychrometrics and analysis of the conditioned zone
    Davanagere, BS
    Sherif, SA
    Goswami, DY
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 1999, 23 (01) : 7 - 21
  • [7] Experimental investigation on desiccant air-conditioning system in India
    Mittal V.
    Khan B.K.
    [J]. Frontiers of Energy and Power Engineering in China, 2010, 4 (2): : 161 - 165
  • [8] Control strategies for a liquid desiccant air-conditioning system
    Ge, Gaoming
    Xiao, Fu
    Niu, Xiaofeng
    [J]. ENERGY AND BUILDINGS, 2011, 43 (06) : 1499 - 1507
  • [9] Feasibility study on power ultrasound for regeneration of silica gel-A potential desiccant used in air-conditioning system
    Yao, Ye
    Zhang, Weijiang
    Li, Shiqing
    [J]. APPLIED ENERGY, 2009, 86 (11) : 2394 - 2400
  • [10] Feasibility study of using agriculture waste as desiccant for air conditioning system
    Khedari, J
    Rawangkul, R
    Chimchavee, W
    Hirunlabh, J
    Watanasungsuit, A
    [J]. RENEWABLE ENERGY, 2003, 28 (10) : 1617 - 1628