Modeling and dynamic simulations of doubly fed adjustable-speed pumped storage units

被引:100
|
作者
Lung, Jen-Kuang [1 ]
Lu, Ying
Hung, Wen-Lung
Kao, Wen-Shiow
机构
[1] Natl Taipei Univ Technol, Dept Elect Engn, Taipei 106, Taiwan
[2] St Johns Univ, Dept Comp & Commun Engn, Taipei 251, Taiwan
[3] Taiwan Power Co, Dept Generat, Taipei 10963, Taiwan
关键词
cyclo-converter; doubly fed adjustable-speed; pumped storage unit (DFASPSU); frequency control;
D O I
10.1109/TEC.2006.875481
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper derives the mathematical models of doubly fed adjustable-speed pumped storage units (DFASPSUs) to be utilized in the power system analysis. It adopts the improved induction machine model with ac excitation on the wire-wound rotor as well as the field-oriented control theory for the study and analysis of DFASPSU models. First, the rotor excitation voltage is separated into two components, Le., the q-axis voltage and the d-axis voltage, so as to control the output active and reactive powers, respectively. Next, a dynamic model of DFASPSU is derived using the swing equation of rotary electric machine and the equation of motion of rotor rotating mass. Finally, computer simulation is carried out to compare its results with practical examples in terms of dynamic characteristics for Verifying the correctness of the proposed models.
引用
下载
收藏
页码:250 / 258
页数:9
相关论文
共 50 条
  • [1] Adjustable-speed operation of doubly fed machines in pumped storage power plants
    Bendl, J
    Chomát, M
    Schreier, L
    NINTH INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND DRIVES, 1999, (468): : 223 - 227
  • [2] Dynamic Modeling of Adjustable-Speed Pumped Storage Hydropower Plant
    Muljadi, E.
    Singh, M.
    Gevorgian, V.
    Mohanpurkar, M.
    Hovsapian, R.
    Koritarov, V.
    2015 IEEE POWER & ENERGY SOCIETY GENERAL MEETING, 2015,
  • [3] Model-based Control for Doubly Fed Adjustable-Speed Pumped Storage Units with Fast Power Support
    Hu, Weizhi
    Zhang, Pinjia
    Chen, Zijun
    Li, Juan
    Chen, Songsong
    Ruan, Wenjun
    PROCEEDINGS OF THE 2018 13TH IEEE CONFERENCE ON INDUSTRIAL ELECTRONICS AND APPLICATIONS (ICIEA 2018), 2018, : 2227 - 2232
  • [4] Working regions of adjustable-speed units with doubly fed machines
    Schreier, L
    Chomát, M
    Bendl, J
    IEMDC'99 - IEEE INTERNATIONAL ELECTRIC MACHINES AND DRIVES CONFERENCE, PROCEEDINGS, 1999, : 457 - 459
  • [5] Reactive Power Characteristic Analysis of Doubly-fed Adjustable-speed Pumped Storage Unit
    Wang X.
    Han M.
    Teshager B.G.
    Dianwang Jishu/Power System Technology, 2019, 43 (08): : 2918 - 2924
  • [6] A Novel Method to Analyze the Reactive Power Characteristic of Doubly Fed Adjustable-Speed Pumped Storage Unit
    Wang, Xinzhu
    Han, Minxiao
    Teshager, Bitew Girmaw
    2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 4143 - 4148
  • [7] A Comparison of the Dynamic Performance of Conventional and Adjustable-Speed Pumped Storage Hydro
    Nag, Soumyadeep
    Lee, Kwang Y.
    2021 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2021,
  • [8] Dynamic Modeling of Full Converter Adjustable-speed Pumped Storage Hydropower (FC AS-PSH)
    Dong, Zerui
    Muljadi, Eduard
    Kim, Jinho
    Nelms, Robert M.
    2020 IEEE POWER & ENERGY SOCIETY GENERAL MEETING (PESGM), 2020,
  • [9] Adjustable-speed power unit with doubly FED machine
    Chomát, Miroslav
    Schreier, Ludek
    Bendl, Jirí
    Acta Technica CSAV (Ceskoslovensk Akademie Ved), 2002, 47 (01): : 1 - 12
  • [10] Computer simulations of dynamic performance of 400 MW adjustable speed pumped storage units
    Kita, E
    Nakagawa, H
    Kuwabara, T
    Harada, M
    HYDRAULIC MACHINERY AND CAVITATION, VOLS I AND II, 1996, : 1073 - 1082