Water Tree Deterioration Diagnosis for 10 kV XLPE cable based on Residual Charge Method

被引:3
|
作者
Du, B. X. [1 ]
Huo, Z. X. [1 ]
Li, H. B. [1 ]
Gao, Y. [1 ]
机构
[1] Tianjin Univ, Key Lab Power Syst Simulat & Control, Minist Educ, Sch Elect Engn & Automat, Tianjin 300072, Peoples R China
关键词
XLPE cable; water tree; Residual Charge Method; pulse;
D O I
10.1109/ICPADM.2009.5252400
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
XLPE cables are widely used in urban distribution systems because of their excellent mechanical, heat and electrical properties. However, water tree, formed due to the existence of water and intense electric field, is one of the primary causes of aging breakdown. There used to be several methods, such as insulation impedance method and DC leakage current method for the detection of bridged water tree, which are non-effective for the diagnosis of non-bridged one. Residual Charge Method is known for its effectiveness in the diagnosis of non-bridged one. In this paper, pulse voltage is applied to the DC voltage charged XLPE cable after grounding. It is called 'Pulsed-type Residual Charge Method' which is found to be more effective for the diagnosis of non-bridged water tree. The effects of DC voltage, grounding time and pulse voltage on the amount of residual charge are Studied. Also, the releasing mechanism of residual charge by pulse is discussed. Accumulated results Show that the improved method has a high resolution for the diagnosis of water tree degradation degree.
引用
收藏
页码:417 / 420
页数:4
相关论文
共 50 条
  • [1] Deterioration Analysis of Ex-Serviced 110 kV XLPE Cable Based on Residual Charge Method
    Du, B. X.
    Li, Hongbo
    Gao, Yu
    Wang, Li
    Huo, Zhenxing
    [J]. CEIDP: 2009 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, 2009, : 638 - +
  • [3] Study on Charge Dynamics in Water-Tree XLPE Insulation for Deterioration Diagnosis
    Ra, Nhet
    Futami, Hiroyuki
    Kawashima, Tomohiro
    Murakami, Yoshinobu
    Hozumi, Naohiro
    Kurihara, Takashi
    Okamoto, Tatsuki
    [J]. 2017 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM), VOLS 1 & 2, 2017, : 343 - 346
  • [4] Study on Water Tree Degradation Diagnosis of XLPE Cable Using Charge Radar
    Kim, MyonHwan
    Unoki, Taketo
    Murakami, Yoshinobu
    Nagao, Masayuki
    Kurihara, Takashi
    Okamoto, Tatsuki
    Miyajima, Kazuhisa
    Uchida, Katsumi
    Hozumi, Naohiro
    [J]. PROCEEDINGS OF 2014 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS (ISEIM 2014), 2014, : 148 - 151
  • [5] Dielectric spectroscopy for diagnosis of water tree deterioration in XLPE cables
    Werelius, P
    Thärning, P
    Eriksson, R
    Holmgren, B
    Gäfvert, U
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2001, 8 (01) : 27 - 42
  • [6] Diagnosis and restoration of water tree aged XLPE cable materials
    Faremo, H
    Ildstad, E
    [J]. CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1996, : 596 - 599
  • [7] Measurement of Residual Charge using Pulse Voltages for Water Tree Degraded XLPE Cables Diagnosis
    Kurihara, Takashi
    Okamoto, Tatsuki
    Kim, Myong Hwan
    Hozumi, Naohiro
    Tsuji, Taizo
    Uchida, Katsumi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2014, 21 (01) : 321 - 330
  • [8] Charge-Simulation-Based Electric Field Analysis and Electrical Tree Propagation Model with Defects in 10 kV XLPE Cable Joint
    He, Jiahong
    He, Kang
    Cui, Longfei
    [J]. ENERGIES, 2019, 12 (23)
  • [9] A Novel 10kV XLPE Cable Failure Prediction Method
    Mao Jun
    Tang HuiDong
    [J]. MACHINERY, MATERIALS SCIENCE AND ENERGY ENGINEERING, 2015, : 58 - 64
  • [10] Study on Diagnostic Method of Aging 10kV XLPE Cable
    Fan Weinan
    Huang Yanguang
    Zhang Yaru
    Xiong Jun
    Wang Yong
    You Jiao
    Zhu Bin
    Jia Zhidong
    [J]. 2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,