Influence of air inlet/outlet arrangement of displacement ventilation on local environment control for unearthed relics within site museum

被引:22
|
作者
Luo, Xilian [1 ]
Huang, Xingyu [1 ]
Feng, Zhuangbo [2 ]
Li, Juan [1 ]
Gu, Zhaolin [1 ]
机构
[1] Xi An Jiao Tong Univ, Sch Human Settlements & Civil Engn, Xian 710049, Peoples R China
[2] Southeast Univ, Sch Architecture, Nanjing 21009, Peoples R China
基金
中国国家自然科学基金;
关键词
Displacement ventilation; Large space exhibition hall; Relic conservation; Soil-air coupling environment; INDOOR ENVIRONMENT; ENERGY; PRESERVATION; IMPACT; HVAC; CONSERVATION; TEMPERATURE; STRATEGIES; ARTIFACTS; QUALITY;
D O I
10.1016/j.enbuild.2021.111116
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Displacement ventilation system is a proven way to save energy by controlling the local preservation environment for the unearthed relics in site museums. In this study, the influences of air inlet/outlet arrangement as well as the earthen site temperature on the performance of the local environment control system were investigated. The results demonstrate that, in addition to achieving a significant reduction in energy consumption, the displacement ventilation system can also achieve local environmental control within the preservation area of a large exhibition hall, while establishing an equilibrium of the soil-air environment. Moreover, by reducing the height of the return air inlet and the effective height of the environmental control area, energy savings of 47.7-65.9% can be achieved. Moving the position of the air supply outlet to the bottom of the pit has little effect on overall environmental control, while adjusting the air supply temperature to match that of the soil at the bottom of the relic preservation area can effectively reduce environmental disturbance, achieving uniformity and environmental stability. These research results provide not only an effective solution for local environmental control of the relics in site museums, but also a basis for the functioning of the displacement ventilation system within the site exhibition hall. (c) 2021 Elsevier B.V. All rights reserved.
引用
收藏
页数:13
相关论文
共 4 条
  • [1] Independent local environment control for visitor and relics area within site museums by displacement ventilation
    Li, Jiaxuan
    Huang, Xingyu
    Chang, Bin
    Feng, Zhuangbo
    Gu, Zhaolin
    Luo, Xilian
    APPLIED THERMAL ENGINEERING, 2024, 257
  • [2] Local attachment ventilation system for the unearthed relic preservation area within site museum
    Dang, Yuexi
    Luo, Xilian
    Chang, Bin
    Huang, Xingyu
    Feng, Zhuangbo
    Gu, Zhaolin
    SUSTAINABLE CITIES AND SOCIETY, 2022, 77
  • [3] Influence of Return-Air Outlet Position on Artifacts’ Preservation Environment with Displacement Ventilation System
    Li J.
    Luo X.
    Chang B.
    Gu Z.
    Hsi-An Chiao Tung Ta Hsueh/Journal of Xi'an Jiaotong University, 2019, 53 (05): : 115 - 122
  • [4] Local heating of a visitor corridor within a large site museum exhibition hall via an integrated jet ventilation and air curtain system
    Huang, Xingyu
    Luo, Xilian
    Shen, Cong
    Chang, Bin
    Gu, Zhaolin
    JOURNAL OF BUILDING ENGINEERING, 2023, 69