Study on the Design and Operation of an Outdoor Air-Cooling System for a Computer Room

被引:1
|
作者
Hwang, JiHyun [1 ,2 ]
Lee, Taewon [1 ]
机构
[1] Korea Inst Civil Engn & Bldg Technol, Dept Fire Safety Res, Goyang 10223, South Korea
[2] Sungkyunkwan Univ, Dept Construct Environm Syst Engn, Suwon 16419, South Korea
关键词
computer room; outdoor air cooling; design and operation; airflow ratio; energy saving; field application;
D O I
10.3390/en14061670
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
Due to the recent growth of the Internet and the rapid development of information and communications technology, the number of data centers and the amount of power consumed are expected to increase rapidly. However, these data centers consume large amounts of electric power throughout the year, regardless of working days or holidays; hence, measures to save energy at these facilities are urgently required. A numerical analysis was conducted in this study by changing various variables to examine the effects of various design and operating conditions on outdoor air-cooling systems and to derive some operating plans to minimize electric power consumption through the introduction of outside air into the computer room. When designing the system, it is desirable to select airflow considering various factors, such as the heat generated by the computer equipment, the efficiency of the fan, and the performance of the refrigerator, rather than the theoretical maximum outdoor airflow. As a result, the optimal design air volume was calculated according to the equipment load. Consequently, the optimal design air volume of the modeled computer system was obtained as 26,200 m(3)/h. The application of this optimal design air volume is expected to yield an annual energy-saving effect of 56.1% compared with the power consumption in the air-conditioning period during which the application of outdoor air cooling is impossible.
引用
收藏
页数:17
相关论文
共 50 条
  • [1] Outdoor Air-Cooling System for a Computer Room and Its Corresponding Energy-Saving Effect
    Hwang, JiHyun
    Lee, Taewon
    ENERGIES, 2020, 13 (21)
  • [2] NUMERICAL APPROACH TO A MODULARIZED DATA COMPUTER ROOM USING A FRESH AIR-COOLING SYSTEM
    Ma, Jing
    Liu, Yin
    Guan, Ren-Bo
    THERMAL SCIENCE, 2019, 23 (04): : 2421 - 2428
  • [3] Analysis of joint operation of air-cooling system and peak cooling device in summer
    Jin, Yingai
    Xing, Yaohong
    Tian, Cong
    Quan, Mingyu
    Jiang, Yan
    Zhao, Qiang
    APPLIED THERMAL ENGINEERING, 2021, 188
  • [4] Design and operation for the direct air-cooling unit in Yungang power plant
    Li, SH
    Zhang, JB
    Proceedings of the World Engineers' Convention 2004, Vol F-B, Power and Energy, 2004, : 125 - 138
  • [5] Influence of solar radiation on operation of a direct air-cooling condenser system
    Liu, Lihua
    Du, Xiaoze
    Yang, Lijun
    Yang, Yongping
    Li, Pei
    Wu, Shoushan
    Huagong Xuebao/CIESC Journal, 2010, 61 (10): : 2535 - 2539
  • [6] OPERATION OF ATOMIZERS FOR AIR-COOLING REACTORS.
    Okun', A.G.
    Korovina, L.V.
    Shmerkovich, V.M.
    Chemical and Petroleum Engineering, 1983, 19 (1-2) : 67 - 70
  • [7] A design optimization study of an air-cooling battery thermal management system for electric vehicles
    Zhao, Gang
    Wang, Xiaolin
    Negnevitsky, Michael
    Zhang, Hengyun
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART E-JOURNAL OF PROCESS MECHANICAL ENGINEERING, 2023, 237 (04) : 1125 - 1136
  • [8] Air-Cooling Optimization at System Level
    Gradinger, Thomas B.
    PROCEEDINGS OF THE 2011-14TH EUROPEAN CONFERENCE ON POWER ELECTRONICS AND APPLICATIONS (EPE 2011), 2011,
  • [9] Experimental study on air-cooling aggregate
    Chen, Shengping
    Ren Min Chang Jiang/Yangtze River, 1995, 26 (12):
  • [10] An experimental and numerical study of a thermoelectric air-cooling and air-heating system
    Cosnier, Matthieu
    Fraisse, Gilles
    Luo, Lingai
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2008, 31 (06): : 1051 - 1062