Research of Temperature and Humidity Decoupling Control for Central Air-conditioning System

被引:6
|
作者
Zhao, Xianmei [1 ]
Tang, Jie [1 ]
Chen, Dongxian [1 ]
机构
[1] Guangdong Polytech Normal Univ, Guangzhou 510665, Guangdong, Peoples R China
关键词
PID control; central air-conditioning system; temperature and humidity control; transfer function model; decoupling control; MODEL;
D O I
10.1109/IHMSC.2009.224
中图分类号
TP18 [人工智能理论];
学科分类号
081104 ; 0812 ; 0835 ; 1405 ;
摘要
The temperature and humidity decoupling control method was presented in this paper to resolve the coupling problem between temperature and humidify in central air-conditioning variable dew point control system. By introducing absolute humidity as an intermediate variable to control the machine dew point, temperature and humidify of system can be decoupled. Two input and two output transfer function model was established by combining the theoretical analysis with the data analysis of experiment, and a control system consisting of a feed forward compensation decouple control and PID control was designed. The simulation based on MATLAB results demonstrated that this method is effective, and is also effective to control temperature and humidity system.
引用
收藏
页码:404 / 408
页数:5
相关论文
共 50 条
  • [1] Research of Temperature and Humidity Independent Control Air-conditioning System
    Wang, Zibiao
    Zhang, Xiaoying
    [J]. ENERGY AND POWER TECHNOLOGY, PTS 1 AND 2, 2013, 805-806 : 557 - 561
  • [2] The Cognition to the Temperature and Humidity Independent Control Air-conditioning System
    Kuang Daqing
    Niu Runping
    Lv Lina
    Chen Xiaoyi
    [J]. 4TH INTERNATIONAL CONFERENCE ON ADVANCES IN ENERGY RESOURCES AND ENVIRONMENT ENGINEERING, 2019, 237
  • [3] A NEW HOUSEHOLD CENTRAL AIR-CONDITIONING OF TEMPERATURE HUMIDITY INDEPENDENT CONTROL
    Liu, C.
    Zhang, X.
    Yuan, Yuan
    [J]. 23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 2754 - 2761
  • [4] Room temperature and humidity decoupling control of common variable air volume air-conditioning system based on bilinear characteristics
    Zhang Y.
    Yan T.
    Xu X.
    Gao J.
    Huang G.
    [J]. Energy and Built Environment, 2023, 4 (03): : 354 - 367
  • [5] Temperature and humidity control with a model predictive control method in the air-conditioning system
    Liu Jingyun
    Li Ping
    [J]. 2017 INTERNATIONAL CONFERENCE ON ADVANCED MECHATRONIC SYSTEMS (ICAMECHS), 2017, : 408 - 412
  • [6] Research of cascade control with an application to central air-conditioning system
    Wang, Jiang-Jiang
    Zhang, Chun-Fa
    Jing, You-Yin
    [J]. PROCEEDINGS OF 2007 INTERNATIONAL CONFERENCE ON MACHINE LEARNING AND CYBERNETICS, VOLS 1-7, 2007, : 498 - 503
  • [7] Discussion on fresh air volume in Temperature and Humidity Independent Control of Air-conditioning System
    Cheng, Xiaolong
    Liu, Jinxiang
    Wang, Yu
    Yuan, Xiaolei
    Jin, Hui
    [J]. 2018 2ND INTERNATIONAL WORKSHOP ON RENEWABLE ENERGY AND DEVELOPMENT (IWRED 2018), 2018, 153
  • [8] Performance study of a constant temperature and humidity air-conditioning system with temperature and humidity independent control device
    Zhang, X. J.
    Xiao, F.
    Li, S.
    [J]. ENERGY AND BUILDINGS, 2012, 49 : 640 - 646
  • [9] Performance of temperature and humidity independent control air-conditioning system in an office building
    Zhao, Kang
    Liu, Xiao-Hua
    Zhang, Tao
    Jiang, Yi
    [J]. ENERGY AND BUILDINGS, 2011, 43 (08) : 1895 - 1903
  • [10] Automatic temperature and humidity control system using air-conditioning in transformer substation
    Feng, Li
    Hui, Zhou
    Yan, Tao
    [J]. 2012 ASIA-PACIFIC POWER AND ENERGY ENGINEERING CONFERENCE (APPEEC), 2012,