Thermal Breakage of Tempered Glass Fa‡ade with Down-Flowing Water Film Under Different Heating Rates

被引:8
|
作者
Shao, Guangzheng [1 ]
Wang, Qingsong [1 ,2 ]
Zhao, Han [1 ]
Wang, Yu [1 ]
Sun, Jinhua [1 ,2 ]
He, Linghui [1 ]
Wang, Qingsong [1 ,2 ]
Sun, Jinhua [1 ,2 ]
机构
[1] Univ Sci & Technol China, State Key Lab Fire Sci, Hefei 230026, Peoples R China
[2] Collaborat Innovat Ctr Urban Publ Safety, Hefei 230026, Anhui, Peoples R China
基金
中国国家自然科学基金;
关键词
Tempered glass; Thermal breakage; Water film; Heating rate; Fire; WINDOW GLASS; RADIANT EXPOSURE; FIRE; PANE; TRANSMISSION; RESISTANCE; SPRINKLER; SINGLE; FIELDS;
D O I
10.1007/s10694-015-0499-5
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The objective of this work is to investigate the effect of the heating rate on the thermal breakage and fallout behavior of the tempered glass with down-flowing water film. The heating rate of the glass panes was controlled by changing the distance between the fire source and the glazing surface, which ranged from 0.6A degrees C s(-1) to 1.0A degrees C s(-1). N-heptane pool fire was adopted to heat up the glass panes and the fuel pan was positioned 500 or 600 mm away from the exposed glass surface. During the experiments the water film was initiated manually when the maximum glazing temperature reached different designed values. The results show that all the glazing panes kept their integrity when the fire source distance was 500 mm. In contrast, all the glass panes cracked and fell out the frame when the fire source distance was 600 mm except the one with the water film discharged at 200A degrees C. The results illustrate that the heating rate plays a key role on the breakage of glass fa double dagger ades. Under the effect of water film or sprinkler system, glass panes are more likely to fail when exposed to a fire with smaller heat release rate or greater distance, rather than the opposite case.
引用
收藏
页码:563 / 580
页数:18
相关论文
共 7 条
  • [1] Thermal Breakage of Tempered Glass Façade with Down-Flowing Water Film Under Different Heating Rates
    Guangzheng Shao
    Qingsong Wang
    Han Zhao
    Yu Wang
    Jinhua Sun
    Linghui He
    Fire Technology, 2016, 52 : 563 - 580
  • [2] Fire resistance tests of a glass pane with down-flowing water film
    Wu, Chan-Wei
    Lin, Ta-Hui
    Lei, Ming-Yuan
    Chung, Tien-Hsu
    Huang, Chien-Chang
    Chiang, Wei-Tang
    JOURNAL OF THE CHINESE INSTITUTE OF ENGINEERS, 2008, 31 (05) : 737 - 744
  • [3] Thermal breakage and fallout behaviors of non-tempered glass under the effect of water film
    Wang, Qingsong
    Shao, Guangzheng
    Wang, Yu
    Zhao, Han
    Sun, Jinhua
    He, Linghui
    JOURNAL OF FIRE SCIENCES, 2015, 33 (05) : 390 - 404
  • [4] Modeling glass cooling mechanism with down-flowing water film via the smoothed particle hydrodynamics
    Abdoh, D. A.
    Ademiloye, A. S.
    Liew, K. M.
    COMPUTER METHODS IN APPLIED MECHANICS AND ENGINEERING, 2020, 362
  • [5] Estimation of heat-transfer characteristics on the hot surface of glass pane with down-flowing water film
    Chen, Han-Taw
    Lee, Shin-Ku
    BUILDING AND ENVIRONMENT, 2010, 45 (10) : 2089 - 2099
  • [6] A meshfree analysis of the thermal behaviors of hot surface glass pane subjects to down-flowing water film via smoothed particle hydrodynamics
    Abdoh, D. A.
    Ademiloye, A. S.
    Liew, K. M.
    ENGINEERING ANALYSIS WITH BOUNDARY ELEMENTS, 2020, 120 : 195 - 210
  • [7] A meshfree analysis of the thermal behaviors of hot surface glass pane subjects to down-flowing water film via smoothed particle hydrodynamics
    Abdoh D.A.
    Ademiloye A.S.
    Liew K.M.
    Liew, K.M. (kmliew@cityu.edu.hk), 1600, Elsevier Ltd (120): : 195 - 210