Experimental Investigation of Suppression of 18650 Lithium Ion Cell Array Fires with Water Mist

被引:14
|
作者
Said, Ahmed O. [1 ,2 ,3 ]
Garber, Alex [1 ]
Peng, Yang [1 ]
Stoliarov, Stanislav I. [1 ,2 ]
机构
[1] Univ Maryland, Fire Protect Engn Dept, College Pk, MD 20742 USA
[2] Univ Maryland, Mech Engn Dept, College Pk, MD 20742 USA
[3] Worcester Polytech Inst, Fire Protect Engn Dept, Worcester, MA 01605 USA
关键词
Battery pack; Thermal runaway; Cascading failure; Fire suppression; Water mist; Oxygen consumption calorimetry; THERMALLY-INDUCED FAILURE; MECHANISMS; DYNAMICS; IMPACT;
D O I
10.1007/s10694-021-01151-9
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
The effectiveness of suppression of lithium ion battery, LIB, fires with water mist was investigated experimentally using a previously developed bench-scale wind tunnel. The experiments were conducted on lithium ion cell arrays constructed from twelve cylindrical (18,650 form factor), fully charged, lithium cobalt oxide cells, which were densely packed in a rectangular configuration without gaps. An electric heater was employed to initiate thermal runaway in one cell. Failure propagation was then tracked using thermocouples located at the bottom surfaces of the cells. Heat release due to flaming combustion was computed based on the oxygen consumption method. Experiments conducted at 640 l min(-1) of air, 320 l min(-1) of air, and 186 l min(-1) of nitrogen tunnel purge flow were used as reference points. All reference point experiments underwent complete cascading failure. Addition of 1.0 and 1.6 g s(-1) of water mist to 320 and 640 l min(-1) of air produced agent concentrations of 14.1 and 11.1 wt%, respectively, which are slightly above the concentration of water mist recommended for suppression of traditional fires. Application of water mist at 1.0 and 1.6 g s(-1) prevented cascading failure in 40% and 50% of the tests, respectively, and significantly reduced the rate of failure propagation in the other tests. At both water mist delivery rates, flaming combustion associated with burning of battery ejecta was inhibited, reducing the combustion efficiency below 50%. One of the key findings of this study is that suppression of flaming combustion is not sufficient to stop cascading failure. The array must be continually cooled with water mist until the temperature of the cells decreases below a certain threshold, which prevents chemical reactions between battery materials inside the cell casings.
引用
收藏
页码:523 / 551
页数:29
相关论文
共 50 条
  • [1] Experimental Investigation of Suppression of 18650 Lithium Ion Cell Array Fires with Water Mist
    Ahmed O. Said
    Alex Garber
    Yang Peng
    Stanislav I. Stoliarov
    [J]. Fire Technology, 2022, 58 : 523 - 551
  • [2] Experimental study of the cooling effect of water mist on 18650 lithium-ion battery at different initial temperatures
    Xu, Jiajia
    Duan, Qiangling
    Zhang, Lin
    Liu, Yujun
    Zhao, Chunpeng
    Wang, Qingsong
    [J]. PROCESS SAFETY AND ENVIRONMENTAL PROTECTION, 2022, 157 : 156 - 166
  • [3] Experimental Studies on Water Mist Suppression of Liquid Fires with and without Additives
    Cong, Beihua
    Liao, Guangxuan
    [J]. JOURNAL OF FIRE SCIENCES, 2009, 27 (02) : 101 - 123
  • [4] Thermal runaway suppression effect of water mist on 18650-cylinder lithium-ion batteries with different cathode materials
    Liu, Xiaozhao
    Xu, Dengji
    Meng, Xiaokai
    Lu, Zhumao
    Chen, Yanjun
    Liu, Changcheng
    Huang, Que
    [J]. CASE STUDIES IN THERMAL ENGINEERING, 2022, 35
  • [5] Experimental investigation of water spray on suppressing lithium-ion battery fires
    Zhang, Lin
    Duan, Qiangling
    Liu, Yujun
    Xu, Jiajia
    Sun, Jinhua
    Xiao, Huahua
    Wang, Qingsong
    [J]. FIRE SAFETY JOURNAL, 2021, 120
  • [6] Experimental investigation of cascading failure in 18650 lithium ion cell arrays: Impact of cathode chemistry
    Said, Ahmed O.
    Lee, Christopher
    Stoliarov, Stanislav I.
    [J]. JOURNAL OF POWER SOURCES, 2020, 446
  • [7] Fire suppression mechanisms of solid fires with water mist
    State Key Laboratory of Fire Science, University of Science and Technology of China, Hefei 230026, China
    [J]. Ranshao Kexue Yu Jishu, 2007, 1 (40-44):
  • [8] Experimental study on the synergistic effect of gas extinguishing agents and water mist on suppressing lithium-ion battery fires
    Zhang, Lin
    Li, Yongqi
    Duan, Qiangling
    Chen, Man
    Xu, Jiajia
    Zhao, Chunpeng
    Sun, Jinhua
    Wang, Qingsong
    [J]. JOURNAL OF ENERGY STORAGE, 2020, 32
  • [9] LITHIUM-ION BATTERY FIRE SUPPRESSION USING WATER MIST SYSTEMS
    Ghiji, Matt
    Burch, Ian
    Suendermann, Brigitta
    Gamble, Grant
    Novozhilov, Vasily
    Joseph, Paul
    Moinuddin, Khalid
    [J]. FRONTIERS IN HEAT AND MASS TRANSFER, 2021, 17
  • [10] Lithium-ion battery fire suppression using water mist systems
    Ghiji M.
    Burch I.
    Suendermann B.
    Gamble G.
    Novozhilov V.
    Joseph P.
    Moinuddin K.
    [J]. Frontiers in Heat and Mass Transfer, 2021, 17