Methanol Marker for the Detection of Insulating Paper Degradation in Transformer Insulating Oil

被引:23
|
作者
Jalbert, Jocelyn [1 ]
Rodriguez-Celis, Esperanza M. [1 ]
Arroyo-Fernandez, Oscar H. [2 ]
Duchesne, Steve [1 ]
Morin, Brigitte [1 ]
机构
[1] Inst Rech Hydro Quebec IREQ, Varennes, PQ J3X 1S1, Canada
[2] Univ Quebec Chicoutimi UQAC, Res Chair Aging Power Network Infraestruct ViAHT, Chicoutimi, PQ G7H 2B1, Canada
关键词
methanol; cellulose degradation; insulating oil; kinetics; transformers; mechanical properties; postmortem; CHAIN-END GROUPS; FILLED POWER TRANSFORMERS; CELLULOSE DEGRADATION; TENSILE-STRENGTH; EVOLUTION-EQUATIONS; CHEMICAL MARKERS; AGING ASSESSMENT; KINETICS; DEPOLYMERIZATION; ETHANOL;
D O I
10.3390/en12203969
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This manuscript presents a comprehensive literature review with the aim to provide readers a reference document with up-to-date information on the field of methanol use as a chemical marker. It has been a little more than a decade since methanol was first introduced as a marker for assessing solid insulation condition in power transformers. It all started when methanol was identified in the laboratory during thermal ageing tests carried out with oil-immersed insulating papers and was subsequently also identified in transformer field samples. The first publication on the subject was released in 2007 by our research group. This review covers the methanol fundamentals such as the analytical methods for its determination in transformer oil, which is generally performed by headspace gas chromatography with mass spectrometry or flame ionization as a detector. Current standardization efforts for its determination include ASTM working group 30948 and IEC TC10. Kinetic studies have confirmed the relationship between methanol generation, the number of broken 1,4-beta-glycosidic bonds of cellulose and changes in mechanical properties. Laboratory tests have confirmed its stability at different accelerated ageing temperatures. Several utilities have identified methanol during field measurements, case studies on power and some distribution transformers are presented, as well as transformer postmortem investigations. These field-testing results demonstrate its utility in monitoring cellulosic insulation degradation. Recently, a model of methanol interpretation has become available that allows for evaluation of the average degree of polymerization of core type transformer cellulose winding. Methanol has a role as an indicator of cellulosic solid insulation ageing in transformer mineral oil, and it is expected that in the future it will be in routine use by utilities.
引用
收藏
页数:30
相关论文
共 50 条
  • [1] Influence of Transformer Oil Acidity on Insulating Paper Degradation
    Noirhomme, B.
    Lessard, M. -C.
    Jalbert, J.
    Besner, S.
    Brochu, F.
    Dupuis, E.
    [J]. 2013 IEEE ELECTRICAL INSULATION CONFERENCE (EIC), 2013, : 392 - 396
  • [2] Indirect Detection of DP for Insulating Paper Based on Methanol Content in Transformer Oil by Spectroscopic Approach
    Peng, Lei
    Fu, Qiang
    Li, Li
    Lin, Musong
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2019, 26 (01) : 90 - 94
  • [3] Low temperature thermal degradation of cellulosic insulating paper in air and transformer oil
    Soares, S
    Ricardo, NMPS
    Heatley, F
    Rodrigues, E
    [J]. POLYMER INTERNATIONAL, 2001, 50 (03) : 303 - 308
  • [4] Effect of Insulating Oil Degradation on Power Transformer Capacitance
    Habib, Salman
    Ahsan, Q.
    [J]. 2012 7TH INTERNATIONAL CONFERENCE ON ELECTRICAL AND COMPUTER ENGINEERING (ICECE), 2012,
  • [5] Non-destructive measurement of the degradation of transformer insulating paper
    Baird, PJ
    Herman, H
    Stevens, GC
    Jarman, PN
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (02) : 309 - 318
  • [6] Spectroscopic measurement and analysis of water and oil in transformer insulating paper
    Baird, PJ
    Herman, H
    Stevens, GC
    Jarman, PN
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2006, 13 (02) : 293 - 308
  • [7] TESTING TRANSFORMER INSULATING OIL
    MYERS, SD
    KELLY, JJ
    [J]. PLANT ENGINEERING, 1978, 32 (06) : 81 - 85
  • [8] A review on a novel method for aging evaluation of transformer insulating paper based on methanol
    Chen, Qingguo
    Sun, Wei
    Cheng, Song
    Huang, Guokai
    [J]. IET GENERATION TRANSMISSION & DISTRIBUTION, 2023, 17 (09) : 1955 - 1971
  • [9] Temperature Characteristics of Thermal Resistance of Insulating Paper for Oil Immersed Transformer
    Yuan Y.
    Zhao Z.
    Luo C.
    Li C.
    Liang S.
    Li Y.
    [J]. Gaodianya Jishu/High Voltage Engineering, 2019, 45 (06): : 1754 - 1761
  • [10] Experiences with Detection of Transformer Failure Based on Insulating Oil Tests
    Rozga, Pawel
    Piotrowski, Tomasz
    Kozak, Ryszard
    [J]. 2017 IEEE 19TH INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2017,