Analysis and Design of PLL Less Current Control for Weak Grid-Tied LCL-Type Voltage Source Converter

被引:14
|
作者
Maganti, Suresh [1 ]
Padhy, Narayana Prasad [1 ]
机构
[1] Indian Inst Technol Roorkee, Dept Elect Engn, Roorkee 247667, Uttar Pradesh, India
关键词
Conventional current controller; grid-connected converter; impedance model; phase-locked loop (PLL) less current control; small-signal stability; weak grid; DIRECT POWER-CONTROL; PHASE-LOCKED-LOOP; CONTROL STRATEGY; STABILITY ANALYSIS; INPUT-ADMITTANCE; VECTOR CONTROL; CONNECTION; INVERTERS; IMPROVE;
D O I
10.1109/JESTPE.2021.3129804
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
For a weak grid-tied LCL-type converter, the conventional current control interacts with a phase-locked loop (PLL) through the voltage at the point of common coupling (PCC). Thus, the dynamics of PLL deteriorate converter stability, hence leads to system instability issues. To avoid the instability issues due to PLL, a PLL less current control is proposed for LCL-type grid-connected converter with capacitor-current-feedback active damping. The analysis and design of the proposed PLL less current control is presented in this article, and the performance of the proposed control is compared with conventional current control (i.e., PLL without bandpass (BP) filter) and improved conventional control (i.e., PLL + BP filter). A small-signal model is developed by considering the dynamics of the PLL and BP filter to show the impact of the current control parameters on converter output impedance. An impedance-based stability analysis is performed to show the system stability against short circuit ratio (SCR) variation for three different current control scenarios, such as proposed PLL less, PLL with a BP filter, and PLL without BP filter. The proposed current control works in both stiff grid and weak grid environments. It has strong robustness against a wide range of variation in grid impedance and more adaptable to grid frequency changes. The performance of the proposed control is verified during grid voltage harmonics, unbalanced voltage, and grid voltage variations and further validated by comparing with the conventional control. In addition to the features mentioned above, the proposed current control is able to operate stably at SCR = 1. Finally, the experiment shows the superiority of the proposed control over conventional control.
引用
收藏
页码:4026 / 4040
页数:15
相关论文
共 50 条
  • [1] Resonant Feed forward Control for LCL-Type Grid-Tied Inverters in Weak Grid Condition
    Tang, Yu
    Huang, Liuliu
    Zhao, Guoshu
    [J]. 2016 IEEE ENERGY CONVERSION CONGRESS AND EXPOSITION (ECCE), 2016,
  • [2] Improved Design of PLL Controller for LCL-Type Grid-Connected Converter in Weak Grid
    Zhu, Donghai
    Zhou, Shiying
    Zou, Xudong
    Kang, Yong
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2020, 35 (05) : 4715 - 4727
  • [3] Passivity Design for LCL-Type Grid-Tied Inverter Based on The Constraint of Realizing Passivity by Capacitor Current Control
    Li, Shaojie
    Lin, Hua
    Wang, Xingwei
    Su, Tianyi
    Ren, Yuanzhe
    Ding, Haojie
    [J]. 2022 4TH INTERNATIONAL CONFERENCE ON SMART POWER & INTERNET ENERGY SYSTEMS, SPIES, 2022, : 527 - 532
  • [4] An Improved Design of Current Controller for LCL-Type Grid-Connected Converter to Reduce Negative Effect of PLL in Weak Grid
    Zhou, Shiying
    Zou, Xudong
    Zhu, Donghai
    Tong, Li
    Zhao, Yingying
    Kang, Yong
    Yuan, Xiaoming
    [J]. IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2018, 6 (02) : 648 - 663
  • [5] The Stability of LCL-Type Grid-Tied Inverter Based on Repetitive Control and Grid Voltage Feed-Forward
    Xu, Feng
    Zhu, Mingzhe
    Ye, Yongqiang
    [J]. IEEE JOURNAL OF EMERGING AND SELECTED TOPICS IN POWER ELECTRONICS, 2023, 11 (02) : 1496 - 1506
  • [6] Robust Damping Method For Voltage Source Converter with LCL-type Filter Under Weak Grid Conditions
    Liu, Huaiyuan
    Xu, Dianguo
    Li, Lei
    Gao, Qiang
    [J]. CSEE JOURNAL OF POWER AND ENERGY SYSTEMS, 2022, 8 (05): : 1428 - 1437
  • [7] Discrete-Time Modified UDE-Based Current Control for LCL-Type Grid-Tied Inverters
    Wu, Yuheng
    Ye, Yongqiang
    Zhao, Qiangsong
    Cao, Yongfeng
    Xiong, Yongkang
    [J]. IEEE TRANSACTIONS ON INDUSTRIAL ELECTRONICS, 2020, 67 (03) : 2143 - 2154
  • [8] Improved Repetitive Control for an LCL-Type Grid-Tied Inverter with Frequency Adaptive Capability in Microgrids
    Zhang, Hongwei
    Zhao, Qiangsong
    Wang, Shuanghong
    Yue, Xuebin
    [J]. ELECTRONICS, 2023, 12 (07)
  • [9] Passivity Enhancement-Based General Design of Capacitor Current Active Damping for LCL-Type Grid-Tied Inverter
    Li, Shaojie
    Lin, Hua
    [J]. IEEE TRANSACTIONS ON POWER ELECTRONICS, 2023, 38 (07) : 8223 - 8236
  • [10] An Improved Active Damping Method for Enhancing Robustness of LCL-Type, Grid-Tied Inverters under Weak Grid Conditions
    Ke, Shanwen
    Li, Yuren
    [J]. SENSORS, 2023, 23 (19)