Dissolved Gas Analysis (DGA) of Arc Discharge Fault in Transformer Insulation Oils (Ester and Mineral oils)

被引:0
|
作者
Ayalew, Zerye [1 ]
Kobayashi, Kazuo [1 ]
Matsumoto, Satoshi [1 ]
Kato, Masamichi [2 ]
机构
[1] Shibaura Inst Technol, Grad Sch Engn & Sci, Tokyo, Japan
[2] Yuka Ind Co LTD, Tokyo, Japan
关键词
Arc discharge; Dissolved gas analysis; Ester oils; Mineral oil;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Transformer insulation oil is an important liquid for insulating and cooling of transformers. For many years' mineral oil has been used for as an insulating liquid in high voltage transformer. Mineral oil has good dielectric properties, however, due to environmental problem; recently many researchers have been looking for an alternative insulating liquid. Biodegradable and environmentally friendly ester oils have attracted more attention in recent years. This paper presents the experimental results of electrical arc stress on dissolved gases of transformer insulating oils (PFAE, MIDEL 7131 and mineral oil). The generated dissolved gases in the sample oils were examined by dissolved gas analysis (DGA) techniques. The test device used for testing is acrylic tube with a high voltage copper electrode at the top and a ground aluminum electrode at the bottom immersed in the oil. The experimental results from dissolved gas analysis (DGA) indicated that arc fault produce large amounts of hydrogen (H-2) and acetylene (C2H2) with small quantities of methane (CH4), ethylene (C2H4) and ethane (C2H6) for both oils. Acetylene (C2H2) gas is the highest combustible gas generated by arc discharge in both mineral and ester oils. Therefore, there is a possibility that the diagnosis of a transformer filled with ester oil can be done using dissolved gas analysis (DGA) method.
引用
收藏
页码:150 / 153
页数:4
相关论文
共 50 条
  • [1] Dissolved gas analysis (DGA) of epartial discharge fault in bio-degradable transformer insulation oil
    Muhamad, N. A.
    Phung, B. T.
    Blackburn, T. R.
    [J]. 2007 AUSTRALASIAN UNIVERSITIES POWER ENGINEERING, VOLS 1-2, 2007, : 336 - +
  • [2] Fault gas generation in ester based transformer fluids and dissolved gas analysis (DGA)
    Khan, Imadullah
    Wang, Zhongdong
    Dai, Jie
    Cotton, Ian
    Northcote, Susan
    [J]. PROCEEDINGS OF 2008 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS, 2007, : 909 - +
  • [3] DGA comparison between ester and mineral oils
    Perrier, C.
    Marugan, M.
    Saravolac, M.
    Beroual, A.
    [J]. 2011 IEEE INTERNATIONAL CONFERENCE ON DIELECTRIC LIQUIDS (ICDL), 2011,
  • [4] DGA Comparison Between Ester and Mineral Oils
    Perrier, C.
    Marugan, M.
    Beroual, A.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2012, 19 (05) : 1609 - 1614
  • [5] Dissolved Gas Analysis (DGA) of Vegetable Oils under Electrical Stress
    Hamid, M. H. A.
    Ishak, M. T.
    Ariffin, M. M.
    Katim, N. I. A.
    Amin, N. A. M.
    Azis, N.
    [J]. 2017 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND POWER SYSTEMS (ICHVEPS), 2017, : 29 - 34
  • [6] Research on the Dissolved Gas Analysis of Electrical Fault Simulation of Natural Ester Insulating Oils
    Chen Cheng
    Cai Shengwei
    Chen Jiangbo
    Shao Minfeng
    Li Hui
    Yin Jin
    Guo Huihao
    [J]. 2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 467 - 472
  • [7] Partial Discharge Inceptions and Patterns in arc Experienced Transformer Oils
    Suwarno
    Santosh
    [J]. PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 1134 - 1138
  • [8] Comparison of Online and Lab DGA Methods for Condition Assessment of Mineral and Vegetable Transformer Oils
    Wang, X.
    Yi, X.
    Li, S. T.
    Wang, Z. D.
    Hinshaw, J. V.
    Noakhes, J.
    [J]. PROCEEDINGS OF 2012 IEEE INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (IEEE CMD 2012), 2012, : 617 - 620
  • [9] STATIC HEADSPACE GAS-CHROMATOGRAPHIC DETERMINATION OF FAULT GASES DISSOLVED IN TRANSFORMER INSULATING OILS
    LEBLANC, Y
    GILBERT, R
    DUVAL, M
    HUBERT, J
    [J]. JOURNAL OF CHROMATOGRAPHY, 1993, 633 (1-2): : 185 - 193
  • [10] Assessment of transformer insulation system by evaluating partial discharge and dissolved gas analysis
    Verma, P
    Roy, M
    Verma, A
    Bhanot, V
    [J]. JOURNAL OF SCIENTIFIC & INDUSTRIAL RESEARCH, 2005, 64 (04): : 262 - 267