Extremely Low Frequency Magnetic Fields at Electric Facilities of a Hospital

被引:0
|
作者
Vahekoski, Tapio [1 ]
Sankari, Jussi [2 ]
Seppala, Timo [2 ]
Korpinen, Leena [3 ]
机构
[1] Sahkoinsinooritoimisto Matti Leppa Oy, Turku, Finland
[2] Hosp Dist Southwest Finland, Turku, Finland
[3] Tampere Univ Technol, Tampere, Finland
关键词
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the investigation of extremely low frequency magnetic fields at electric facilities of a hospital. We conducted 21 measurements (at electric facilities and other areas, for example, in the lobby and in the corridor). The magnetic fields were from 0.2 mu T to 62.0 mu T. The highest value was measured near the main circuit-breaker of the distribution board. Based on the measurements, the magnetic fields can be more than 50 mu T in the technical areas of a hospital, which can cause disturbances in some medical devices.