On-line partial discharge detection of turbine generator using gigahertz-band spatial phase difference method

被引:0
|
作者
Kawada, M [1 ]
Kawasaki, ZI
Matsu-Ura, K
Kuroki, S
Osawa, T
Tanaka, H
机构
[1] Nagoya Inst Technol, Nagoya, Aichi 466, Japan
[2] Osaka Univ, Suita, Osaka 565, Japan
关键词
GHz-band spatial phase difference; steam turbine generator; on-line partial discharge detection; partial discharge test;
D O I
暂无
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Partial discharge (PD) within voids in solid insulating systems is a symptom and/or a direct cause of a deterioration of stator windings of a turbine generator. The bandwidth of the electromagnetic waves emitted from PD is very broad and ranges to the gigahertz. We developed a new system based on the spatial phase difference method for detecting microwaves (GHz) emitted from PD. In this paper we applied this system to two off-line turbine generators in the overhaul and an on-line turbine generator which has two built-in antennas. On-line PD detection of the turbine generator is very useful for recognizing abnormal and/or deteriorated stator winding insulation without a machine outage. It was found that the detection system was able to detect microwaves emitted from PD in an operating turbine generator. (C) 2000 Scripta Technica.
引用
收藏
页码:38 / 43
页数:6
相关论文
共 25 条
  • [1] Detection of partial discharge in operating turbine generator using GHz-band spatial phase difference method
    Kawada, M
    Kawasaki, ZI
    Matsuura, K
    Kuroki, S
    Osawa, T
    Tanaka, H
    1998 INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATING MATERIALS, PROCEEDINGS, 1998, : 71 - 74
  • [2] A New Proposed Method for Interpretation On-line Partial Discharge Measurements Data of Turbine Generator
    Baboraik, A. M.
    Usachev, A. E.
    Ali, Ziad M.
    JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY, 2020, 15 (03) : 1301 - 1311
  • [3] A New Proposed Method for Interpretation On-line Partial Discharge Measurements Data of Turbine Generator
    A. M. Baboraik
    A. E. Usachev
    Ziad M. Ali
    Journal of Electrical Engineering & Technology, 2020, 15 : 1301 - 1311
  • [4] Use of spatial phase difference method to detect microwaves associated with stator coil partial discharge in a generator
    Kawada, M
    Kawasaki, Z
    Matsuura, K
    Musashiya, T
    Otoba, K
    Kuroki, S
    Moriyama, T
    ELECTRICAL ENGINEERING IN JAPAN, 1997, 121 (02) : 16 - 26
  • [5] Use of spatial phase difference method to detect microwaves associated with stator coil partial discharge in a generator
    Osaka Univ, Japan
    Electr Eng Jpn, 2 (16-26):
  • [6] The importance of phase resolved partial discharge pattern recognition for on-line generator monitoring
    Hudon, C
    Belec, M
    CONFERENCE RECORD OF THE 1998 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1998, : 296 - 300
  • [7] On-line Partial Discharge Detection for High Voltage Rotating Machines Using Inductive Method
    Dauksys, G.
    Jonaitis, A.
    ELEKTRONIKA IR ELEKTROTECHNIKA, 2013, 19 (06) : 37 - 40
  • [8] Method of directional difference balance to suppress electromagnetic interference in on-line monitoring partial discharge in transformer
    Chongqing Univ, Chongqing, China
    Zhongguo Jiguang, 10 (340-344):
  • [9] High capacity motors on-line diagnosis based on ultra wide band partial discharge detection
    Carvajal, A
    Garcia-Colon, VR
    IEEE INTERNATIONAL SYMPOSIUM ON DIAGNOSTICS FOR ELECTRIC MACHINES, POWER ELECTRONICS AND DRIVES, PROCEEDINGS, 2003, : 168 - 170
  • [10] Ultra-wide band antenna for partial discharge detection inside switchgear for on-line monitoring
    Marchal, A.
    Monedero, M.
    Le Thuc, P.
    Staraj, R.
    2018 IEEE CONFERENCE ON ANTENNA MEASUREMENTS & APPLICATIONS (CAMA), 2018,