R407C as an alternative to R22 in vapour compression plant: An experimental study

被引:0
|
作者
Greco, A
Mastrullo, R
Palombo, A
机构
[1] DETEC, Univ. Studi di Napoli Federico II, 80125 Napoli
[2] Institute of Mechanical Engineering, Università di Salerno, Fisciano
[3] DETEC, Univ. di Napoli Frederico II, 80125 Napoli, Piazzale Technio
关键词
ozone depletion effect; drop-in substitutes; R22; R407C;
D O I
10.1002/(SICI)1099-114X(19971010)21:12<1087::AID-ER330>3.0.CO;2-Y
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The problem of HCFC22 phase-out in refrigeration plants is analysed, A comparison is performed between R22 and R407C, The latter seems a promising drop-in substitute. Indeed, its use in existing plants would only require discharge of mineral oil and refilling with a compatible polyolester oil. The experimental tests are performed in a plant consisting in a water-cooled vapor-compression circuit employed for cooling a water-glycol mixture in a closed-loop system. Both the thermodynamic properties and general performance of R407C are comparable with those of R22. The COP, however, is 5-17% lower, As a consequence, in order to provide the same refrigerating load, a plant working with R407C requires higher electric-power consumption. The operational behaviour of R407C is increasingly better with increasing condensation and evaporation temperature. Therefore, R407C is a good R22 substitute in all applications requiring high evaporation temperatures, such as air-conditioning plants. (C) 1997 by John Wiley & Sons, Ltd.