Use of peripheral fins for R-290 charge reduction in split-type residential air-conditioners

被引:7
|
作者
Ribeiro, Guilherme B. [1 ]
Barbosa Jr, Jader R. [2 ]
机构
[1] Aeronaut Inst Technol, Mech Engn Div, Sao Jose Dos Campos, Brazil
[2] Univ Fed Santa Catarina, Mech Engn Dept, Florianopolis, SC, Brazil
关键词
Peripheral fin; Air conditioning; Charge; Propane; FINNED-TUBE EVAPORATORS; HEAT-TRANSFER; EXPERIMENTAL PERFORMANCE; FRICTION CORRELATION; OIL; CONDENSATION; SUBSTITUTE; EQUATIONS; PROPANE; MIXTURE;
D O I
10.1016/j.ijrefrig.2019.06.012
中图分类号
O414.1 [热力学];
学科分类号
摘要
The use of hydrocarbons as refrigerants has increased substantially in the past decades due to more severe regulations on direct and indirect carbon dioxide emissions. However, safety standards related to flammable fluids limit the amount of propane (R-290) used in air-conditioning (AC) systems. In this study, an experimentally validated numerical model for a split-type AC system is employed and, for the first time, an air-side peripheral fin geometry is used in the condenser in an attempt to reduce the refrigerant charge for a given system cooling capacity. To establish a fair basis for comparison, plain, wavy and louvered fins were also investigated in the model. A more realistic assessment of the system performance was achieved by considering the POE ISO 22 oil circulation ratio (OCR) in the computation of the physical properties of the mixture. The results have shown that, for the simulated range, heat exchangers with peripheral fins provided higher values of thermal conductance (UA) and cooling capacity than other types of fins. A substantial decrease in the R-290 mass (as high as 12.13%) was observed when peripheral fin condensers were employed. (C) 2019 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:1 / 6
页数:6
相关论文
共 19 条
  • [1] A mathematical model of critical releasable charge for R290 indoor leakage of split-type household air conditioners
    Ning, Qian
    He, Guogeng
    Xiong, Jun
    Fan, Mingjing
    Li, Xiao
    [J]. BUILDING AND ENVIRONMENT, 2023, 228
  • [2] Thermoeconomic analysis and optimization of residential split-type air conditioners
    Barreira, Eduardo M.
    Negrao, Cezar O. R.
    Hermes, Christian J. L.
    [J]. APPLIED THERMAL ENGINEERING, 2013, 50 (01) : 629 - 636
  • [3] Theoretical and simulation analysis for R290 leakage from split-type air conditioners
    Ning, Qian
    He, Guogeng
    Li, Baofeng
    Li, Tiejun
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2024, 166 : 139 - 148
  • [4] Optimum placement of condensing units of split-type air-conditioners by numerical simulation
    Avara, Abdollah
    Daneshgar, Ehsan
    [J]. ENERGY AND BUILDINGS, 2008, 40 (07) : 1268 - 1272
  • [5] Placement of condensing units of split-type air-conditioners at low-rise residences
    Chow, TT
    Lin, Z
    Yang, XY
    [J]. APPLIED THERMAL ENGINEERING, 2002, 22 (13) : 1431 - 1444
  • [6] COST ANALYSIS OF PRODUCING SPLIT-TYPE AIR CONDITIONERS USING HC-290
    Colbourne, D.
    Croiset, I. C.
    Ederberg, L.
    Usinger, J.
    [J]. 23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 2704 - 2711
  • [7] Testing and simulation of potential energy savings in renewing used split-type and window-type air-conditioners
    Alabdulkarem, Abdullah
    Almutairi, Zeyad
    [J]. BUILDING SERVICES ENGINEERING RESEARCH & TECHNOLOGY, 2020, 41 (05): : 586 - 602
  • [8] A Study of Effects of Surrounding Structures towards Airflow Performance in the Outdoor Unit of Split-type Air-conditioners
    Wei, Eric Phan Tze
    Shukor, Mohd Hamdi Abdul
    [J]. RECENT ADVANCES IN FLUID MECHANICS, 2009, : 15 - 21
  • [9] EXPERIMENTAL STUDY OF R290 ENHANCED SYSTEM PERFORMANCE IN RESIDENTIAL AIR-CONDITIONERS AND HEAT PUMPS
    Xu, B.
    Chen, J. P.
    Qi, Z. G.
    Li, F.
    [J]. 23RD IIR INTERNATIONAL CONGRESS OF REFRIGERATION, 2011, 23 : 1576 - +
  • [10] Indoor leakage test for safety of R-290 split type room air conditioner