Postfault analysis of operation of distance protective relays of power transmission lines

被引:24
|
作者
Izykowski, Jan [1 ]
Rosolowski, Eugeniusz
Saha, Murari Mohan
机构
[1] Wroclaw Tech Univ, PL-50370 Wroclaw, Poland
[2] ABB, SE-72159 Vasteras, Sweden
关键词
algorithms; distance protection; fault analysis; power transmission line; simulation; two-end measurement;
D O I
10.1109/TPWRD.2006.877084
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper deals with the postfault analysis of the operation of distance protective relays from the line terminals. The signals of the digital distance relays are processed in the offline regime with the aim of evaluating the particular relay operation case. First, the program enables imitating the fault-loop impedance measurements of the distance relays. Second, the two-end unsynchronized measurements of the relays are considered. The unknown synchronization angle is determined by using the developed noniterative procedure. Then, the distance to fault is calculated. It is applied for calculating the actual values of impedance for the line sections. Comparing the results of these two ways performs analysis of operation of the relays under resistive fault cases. The described postfault analysis algorithm has been tested with the fault data obtained from versatile Alternative Transients Program-Electromagnetic Transients Program simulations. The examples are reported and discussed.
引用
收藏
页码:74 / 81
页数:8
相关论文
共 50 条
  • [1] Post-fault analysis of operation of distance protective relays of power transmission lines
    Izykowski, Jan
    Rosolowski, Eugeniusz
    Saha, Murari
    [J]. 2006 POWER ENGINEERING SOCIETY GENERAL MEETING, VOLS 1-9, 2006, : 2063 - +
  • [2] An ANN-based distance protective relays of transmission lines
    Li, YL
    Li, B
    Zhang, XH
    He, JL
    [J]. SEVENTH INTERNATIONAL CONFERENCE ON DEVELOPMENTS IN POWER SYSTEM PROTECTION, 2001, (479): : 311 - 314
  • [3] An unblocking assistance to distance relays protecting TCSC compensated transmission lines during power swing
    Biswas, Sauvik
    Nayak, Paresh Kumar
    [J]. INTERNATIONAL TRANSACTIONS ON ELECTRICAL ENERGY SYSTEMS, 2019, 29 (08):
  • [4] Performance of distance relays on shunt - FACTS compensated transmission lines
    Sidhu, TS
    Varma, RK
    Gangadharan, PK
    Albasri, FA
    Ortiz, GR
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) : 1837 - 1845
  • [5] Enhanced performance for distance relays due to series capacitors in transmission lines
    Trujillo Guajardo, L. A.
    Conde Enriquez, A.
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 2014, 109 : 20 - 31
  • [6] Analysis of static characteristics of distance relays for UHV lines
    Liu, Shiming
    Li, Xiaobin
    [J]. Dianli Xitong Zidonghua/Automation of Electric Power Systems, 2010, 34 (02): : 75 - 79
  • [7] Management Relay for Assisting Distance Relays in Series Compensated Transmission Lines
    Emre Elmaci
    Fatih M. Nuroglu
    [J]. Arabian Journal for Science and Engineering, 2023, 48 : 6903 - 6913
  • [8] Management Relay for Assisting Distance Relays in Series Compensated Transmission Lines
    Elmaci, Emre
    Nuroglu, Fatih M.
    [J]. ARABIAN JOURNAL FOR SCIENCE AND ENGINEERING, 2023, 48 (05) : 6903 - 6913
  • [9] The impact of current transformers saturation on operation of transmission lines protection relays
    Solak, Krzysztof
    Rebizant, Waldemar
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2010, 86 (11A): : 303 - 307
  • [10] A Hybrid Network IDS for Protective Digital Relays in the Power Transmission Grid
    Koutsandria, Georgia
    Muthukumar, Vishak
    Parvania, Masood
    Peisert, Sean
    McParland, Chuck
    Scaglione, Anna
    [J]. 2014 IEEE INTERNATIONAL CONFERENCE ON SMART GRID COMMUNICATIONS (SMARTGRIDCOMM), 2014, : 908 - 913