Influence of moisture and partial discharges on the degradation of high-voltage surge arresters

被引:23
|
作者
Chrzan, KL [1 ]
机构
[1] Wroclaw Univ Technol, Inst 1 7, PL-50370 Wroclaw, Poland
[2] Univ Wales Coll Cardiff, Sch Engn, Cardiff CF25 0YF, S Glam, Wales
来源
关键词
metal oxide varistors; voltage-current characteristics;
D O I
10.1002/etep.15
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper reports the influence of moisture and internal partial discharges on the degradation of metal oxide varistors in high-voltage surge arresters. Both factors cause an increase in the varistor current under the operating voltage. This phenomenon is dangerous and can cause a total outage of the metal oxide arrester. In the field the moisture ingress can lead to internal discharges. Owing to recovery processes the changes in the voltage-current characteristics of varistors caused by moisture or partial discharges decrease in dry and partial discharge free conditions. The interesting behaviour of some varistors which were degraded by partial discharges was observed. Copyright (C) 2004 John Wiley Sons, Ltd.
引用
收藏
页码:175 / 184
页数:10
相关论文
共 50 条
  • [1] SURGE ARRESTERS FOR HIGH-VOLTAGE SWITCHGEAR.
    Crucius, Michael
    Reichelt, Klaus
    [J]. Siemens power engineering, 1981, 3 (Spec Issue): : 87 - 92
  • [2] SURGE ARRESTERS FOR LIMITING OVERVOLTAGES IN HIGH-VOLTAGE SYSTEMS
    MAYER, A
    [J]. BROWN BOVERI REVIEW, 1983, 70 (1-2): : 48 - 52
  • [3] Partial discharges in high-voltage insulation of turbogenerators
    Klasna, Jan
    Martinek, Petr
    Fanta, Radek
    Pihera, Josef
    [J]. PROCEEDINGS OF THE 2010 IEEE INTERNATIONAL CONFERENCE ON SOLID DIELECTRICS (ICSD 2010), 2010,
  • [4] PARTIAL DISCHARGES IN INSULATION OF HIGH-VOLTAGE TRANSFORMERS
    GURIN, VG
    KALINICHENKO, IS
    KAPLAN, DA
    KONTOROVICH, AM
    KUCHINSKII, GS
    LEVIT, AG
    TATARENKO, YB
    SHCHIPUNOVA, NP
    [J]. ELECTRICAL TECHNOLOGY RUSSIA, 1971, 1 : 95 - +
  • [5] COMPARISON OF THE CAPABILITIES OF METAL-OXIDE AND CONVENTIONAL HIGH-VOLTAGE SURGE ARRESTERS
    STJEAN, G
    LATOUR, Y
    [J]. ELECTRIC POWER SYSTEMS RESEARCH, 1984, 7 (01) : 45 - 52
  • [6] Effect of the grounding resistance to the behaviour of high-voltage transmission lines' surge arresters
    Christodoulou, Christos A.
    Ekonomou, Lambros
    Papanikolaou, Nikolaos
    Gonos, Ioannis F.
    [J]. IET SCIENCE MEASUREMENT & TECHNOLOGY, 2014, 8 (06) : 470 - 478
  • [7] The influence of a magnetic field on the dynamics of partial discharges in high-voltage insulation systems
    Florkowski, Marek
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2024, 100 (04): : 49 - 54
  • [8] Suppression of Partial Discharges in High-Voltage Rotating Machines
    Chapman, M.
    Bruetsch, R.
    [J]. 2009 IEEE ELECTRICAL INSULATION CONFERENCE, 2009, : 338 - +
  • [10] Fault simulation for gapless high voltage surge arresters
    Paplinski, Piotr
    Wankowicz, Jacek
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (11B): : 182 - 184