Energy and exergy evaluation of triple-effect H2O/LiBr absorption cooling system

被引:6
|
作者
Solanki, Alka [1 ]
Pal, Yash [2 ]
机构
[1] Natl Inst Technol Kuruksherta, Sch Renewable Energy & Efficiency, Kuruksherta, Haryana, India
[2] Natl Inst Technol Kurukhetra, Elect Engn Dept, Kurukhetra, Haryana, India
关键词
Triple effect; absorption; exergy analysis; performance; water-lithium bromide; LITHIUM BROMIDE; WORKING FLUIDS; WATER; REFRIGERATION; OPTIMIZATION; SINGLE; TEMPERATURE;
D O I
10.1080/01430750.2020.1831598
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
This paper deals with the energy and exergy analysis of triple-effect LiBr-water absorption system. Mathematical models have been developed using an engineering equation solver (EES) to simulate the triple-effect absorption cycle. The coefficient of performance, exergy efficiency and total exergy destruction are determined by varying generator, absorber and evaporator temperatures. The operating parameters are selected as generator temperature (170-200 degrees C), absorber temperature (25-40 degrees C) and evaporator temperature (5-11 degrees C). Findings illustrate that COP of triple-effect absorption cycle increases at absorption temperatures 35 degrees C and 40 degrees C. For a given evaporator and generator temperature, COP and exergy efficiency of triple absorption cycle increase. The total exergy destruction rate decreases with an increase in evaporator temperature. Largest exergy destruction and exergy percentage are found in absorber and smallest in medium pressure generator.
引用
收藏
页码:3626 / 3637
页数:12
相关论文
共 50 条
  • [1] Simulation of the compressor-assisted triple-effect H2O/LiBr absorption cooling cycles
    Kim, JS
    Ziegler, F
    Lee, H
    APPLIED THERMAL ENGINEERING, 2002, 22 (03) : 295 - 308
  • [2] Simulation of a double effect LiBr/H2O absorption cooling system
    Wardono, B
    Nelson, RM
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1996, 38 (10): : 32 - &
  • [3] ENERGY AND EXERGY ANALYSIS OF A DOUBLE EFFECT PARALLEL FLOW LIBR/H2O ABSORPTION REFRIGERATION SYSTEM
    Arora, Akhilesh
    Dixit, Manoj
    Kaushik, S. C.
    JOURNAL OF THERMAL ENGINEERING, 2016, 2 (01): : 541 - 549
  • [4] COP optimisation of a triple-effect H2O/LiBr absorption cycle under off-design conditions
    Lizarte, R.
    Marcos, J. D.
    APPLIED THERMAL ENGINEERING, 2016, 99 : 195 - 205
  • [5] Simulation of a double-effect LiBr/H2O absorption cooling system
    Wardono, Bagas
    Nelson, Ron M.
    ASHRAE Journal, 1996, 38 (10) : 32 - 38
  • [6] Energy and exergy analyses of LiBr/H2O absorption cooling system having recto-trapezoidal profile absorber plate
    Roy, Rahul
    Kundu, Balaram
    PROCEEDINGS OF THE INSTITUTION OF MECHANICAL ENGINEERS PART C-JOURNAL OF MECHANICAL ENGINEERING SCIENCE, 2021, 235 (15) : 2851 - 2873
  • [7] A STUDY ON CARBON STEEL CORROSION FOR THE DEVELOPMENT OF LIBR-H2O TRIPLE-EFFECT ABSORPTION CHILLERS
    Park, Jeongmin
    Jeong, Siyoung
    5TH IIR INTERNATIONAL CONFERENCE ON THERMOPHYSICAL PROPERTIES AND TRANSFER PROCESSES OF REFRIGERANTS (TPTPR), 2017, : 1106 - 1113
  • [8] Performance Evaluation of 35 kW LiBr - H2O Solar Absorption Cooling System in Thailand
    Ketjoy, Nipon
    Yongphayoon, Rawipa
    Mansiri, Kongrit
    10TH ECO-ENERGY AND MATERIALS SCIENCE AND ENGINEERING SYMPOSIUM, 2013, 34 : 198 - 210
  • [9] A STUDY ON CARBON STEEL CORROSION FOR THE DEVELOPMENT OF LIBR-H2O TRIPLE-EFFECT ABSORPTION CHILLERS
    Park, Jeongmin
    Jeong, Siyoung
    5TH IIR INTERNATIONAL CONFERENCE ON THERMOPHYSICAL PROPERTIES AND TRANSFER PROCESSES OF REFRIGERANTS (TPTPR), 2017, : 451 - 458
  • [10] EXERGY ANALYSIS OF AN SINGLE-EFFECT ABSORPTION REFRIGERATION SYSTEM OPERATING WITH THE LiBr/H2O PAIR
    Gomes Almeida, Igor Marcel
    Formiga Barbosa, Cleiton Rubens
    Oliveira Fontes, Francisco de Assis
    HOLOS, 2010, 26 (03) : 69 - 81