Preliminary experimental results on the R134a refrigeration system using a two-phase ejector as an expander

被引:65
|
作者
Ersoy, H. Kursad [1 ]
Sag, Nagihan Bilir [1 ]
机构
[1] Selcuk Univ, Fac Engn, Dept Mech Engn, TR-42250 Konya, Turkey
关键词
Refrigeration; Ejector; Throttling; Expansion; COP; R134a; PERFORMANCE-CHARACTERISTICS; CYCLE; IMPROVEMENTS; EFFICIENCIES;
D O I
10.1016/j.ijrefrig.2014.04.006
中图分类号
O414.1 [热力学];
学科分类号
摘要
The use of an ejector as an expansion device instead of an expansion valve for expansion work recovery in a vapor-compression cycle was experimentally investigated. The coefficient of performance (COP) values for both conventional and ejector systems were experimentally investigated under the same external conditions. It was observed that, although the drop in the refrigerant pressure in the evaporator of the ejector system was almost negligible, it rose as high as 133 kPa in the conventional system. Depending on the operating conditions, it was found that the work recovery in the ejector was between 14% and 17%. It was also found that the refrigeration system with an ejector as the expander exhibited a COP that was 6.2-14.5% higher than that of the conventional system. The experimental results were found to comply with the theoretical results within an error of approximately 10%. (C) 2014 Elsevier Ltd and IIR. All rights reserved.
引用
收藏
页码:97 / 110
页数:14
相关论文
共 50 条
  • [1] Experimental performances of a two-phase R134a ejector
    Ameur, K.
    Aidoun, Z.
    Ouzzane, M.
    [J]. EXPERIMENTAL THERMAL AND FLUID SCIENCE, 2018, 97 : 12 - 20
  • [2] Experimental investigations on a R134a ejector applied in a refrigeration system
    Yan, Jiwei
    Chen, Guangming
    Liu, Chengyan
    Tang, Liming
    Chen, Qi
    [J]. APPLIED THERMAL ENGINEERING, 2017, 110 : 1061 - 1065
  • [3] Experimental investigation on R134a vapour ejector refrigeration system
    Selvaraju, A.
    Mani, A.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2006, 29 (07): : 1160 - 1166
  • [4] Experimental study on R-134a refrigeration system using a two-phase ejector as an expansion device
    Chaiwongsa, Praitoon
    Wongwises, Somchai
    [J]. APPLIED THERMAL ENGINEERING, 2008, 28 (5-6) : 467 - 477
  • [5] Experimental investigation on a R134a ejector refrigeration system under overall modes
    Li, Fenglei
    Li, Rongrong
    Li, Xinchang
    Tian, Qi
    [J]. APPLIED THERMAL ENGINEERING, 2018, 137 : 784 - 791
  • [6] Numerical study for the design optimization of a two-phase ejector with R134a refrigerant
    Baek, Sunghoon
    Song, Simon
    [J]. JOURNAL OF MECHANICAL SCIENCE AND TECHNOLOGY, 2018, 32 (09) : 4231 - 4236
  • [7] Numerical study for the design optimization of a two-phase ejector with R134a refrigerant
    Sunghoon Baek
    Simon Song
    [J]. Journal of Mechanical Science and Technology, 2018, 32 : 4231 - 4236
  • [8] Study of a solar booster assisted ejector refrigeration system with R134a
    Hernández, JI
    Best, R
    Dorantes, RJ
    Estrada, CA
    [J]. JOURNAL OF SOLAR ENERGY ENGINEERING-TRANSACTIONS OF THE ASME, 2005, 127 (01): : 53 - 59
  • [9] Ejector design and theoretical study of R134a ejector refrigeration cycle
    Khalil, A.
    Fatouh, M.
    Elgendy, E.
    [J]. INTERNATIONAL JOURNAL OF REFRIGERATION, 2011, 34 (07) : 1684 - 1698