Active acoustic noise control in ducts

被引:0
|
作者
Morais, Filipe [1 ]
da Costa, J. M. Sa [1 ]
机构
[1] Univ Tecn Lisboa, Dept Mech Engn, Inst Super Tecn, GCAR IDMEC, Av Rovisco Pais, P-1049001 Lisbon, Portugal
关键词
active noise control; feedforward control; filtered-reference LMS; modified filtered-reference LMS; filtered-u; frequency domain filtered-reference LMS;
D O I
10.1007/1-4020-4543-3_33
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
In this paper existing classical and advanced techniques of active acoustic noise cancellation (ANC) in ducts are collected and compared. The laboratory plant used in experience showed a linear behaviour and so the advanced techniques were not used. Due to delay on the plant, the feedback classical techniques could not be applied. The best results were obtained with the modified filtered-reference LMS (MFX-LMS) and filtered-u techniques. A very important conclusion is that the quadratic normalisation is needed to maintain the algorithms always stable. In this paper 18dB of attenuation of white noise and 35 dB of attenuation of tonal noise were achieved. Thus, ANC can be applied in a real situation resulting in important noise attenuations.
引用
收藏
页码:273 / +
页数:2
相关论文
共 50 条