Cooling of office buildings in cold climates using direct ground-coupled active chilled beams

被引:15
|
作者
Arghand, Taha [1 ]
Javed, Saqib [1 ]
Truschel, Anders [1 ]
Dalenback, Jan-Olof [1 ]
机构
[1] Chalmers Univ Technol, Dept Architecture & Civil Engn, Div Bldg Serv Engn, S-41296 Gothenburg, Sweden
关键词
Direct ground cooling system; High-temperature cooling; Borehole heat exchanger; Active chilled beam; Design optimisation; HEAT-EXCHANGERS; SYSTEMS; PERFORMANCE; DESIGN;
D O I
10.1016/j.renene.2020.09.066
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This study investigates the use of a direct ground cooling system (DGCS) using active chilled beams for the cooling of office buildings in Sweden. The methodology of the study entails laboratory experiments to develop and validate a simulation model of the cooling system. The sensitivity of the input parameters, such as borehole heat exchanger (BHE) length, internal heat gains and room temperature set point, are studied with respect to BHE outlet fluid temperature and room thermal comfort. The results provide a practical insight into designing DGCSs with regard to borehole outlet fluid temperatures. The results also show that the thermal comfort criteria in the room are met by applying the DGCS even under the most critical design conditions of undisturbed ground temperature and internal heat gains. The sensitivity study quantifies the influence of the room temperature setpoint and internal heat gain intensity on the BHE length. The BHE outlet temperature level is more sensitive in shorter BHEs than in the longer ones, and BHE length and room temperature levels are highly correlated. Thus, the sizing of DGCS can benefit from a control system to allow the room temperature to float within a certain range. (C) 2020 The Authors. Published by Elsevier Ltd.
引用
收藏
页码:122 / 132
页数:11
相关论文
共 16 条
  • [1] Performance evaluation of a direct ground-coupled self-regulating active chilled beam system
    Filipsson, Peter
    Truschel, Anders
    Graslund, Jonas
    Dalenback, Jan-Olof
    [J]. ENERGY AND BUILDINGS, 2020, 209
  • [2] Control methods for a direct-ground cooling system: An experimental study on office cooling with ground-coupled ceiling cooling panels
    Arghand, Taha
    Javed, Saqib
    Truschel, Anders
    Dalenback, Jan-Olof
    [J]. ENERGY AND BUILDINGS, 2019, 197 : 47 - 56
  • [3] A comparative study on borehole heat exchanger size for direct ground coupled cooling systems using active chilled beams and TABS
    Arghand, Taha
    Javed, Saqib
    Truschel, Anders
    Dalenback, Jan-Olof
    [J]. ENERGY AND BUILDINGS, 2021, 240
  • [4] Potential cooling savings from a ground-coupled return-air duct system for residential buildings in hot and humid climates
    Do, Sung Lok
    Baltazar, Juan-Carlos
    Haberl, Jeff
    [J]. ENERGY AND BUILDINGS, 2015, 103 : 206 - 215
  • [5] Energy renovation strategies for office buildings using direct ground cooling systems
    Arghand, Taha
    Javed, Saqib
    Truschel, Anders
    Dalenback, Jan-olof
    [J]. SCIENCE AND TECHNOLOGY FOR THE BUILT ENVIRONMENT, 2021, 27 (07) : 874 - 891
  • [6] Influence of system operation on the design and performance of a direct ground-coupled cooling system
    Arghand, Taha
    Javed, Saqib
    Truschel, Anders
    Dalenback, Jan-Olof
    [J]. ENERGY AND BUILDINGS, 2021, 234
  • [7] Night ventilation and active cooling coupled operation for large supermarkets in cold climates
    Li-Xia, Wu
    Jia-Ning, Zhao
    Zhao-Jun, Wang
    [J]. ENERGY AND BUILDINGS, 2006, 38 (12) : 1409 - 1416
  • [8] Adaptation of adsorption cooling system for hot and dry climates: Use of ground water heat exchanger coupled to direct evaporative cooling tower
    Kheireddine, Mohamed-Abdelbassit
    Benchabane, Adel
    Rouag, Amar
    Mahbubul, I. M.
    Arici, Muslum
    Demir, Hakan
    Sevindir, Mustafa Kemal
    [J]. ENERGY SOURCES PART A-RECOVERY UTILIZATION AND ENVIRONMENTAL EFFECTS, 2023, 45 (03) : 9133 - 9148
  • [9] Application of a variable-speed ground-coupled liquid desiccant air-conditioner to multi-story office buildings in temperate regions
    Lee, C. K.
    Lam, H. N.
    [J]. INTERNATIONAL JOURNAL OF GREEN ENERGY, 2016, 13 (01) : 85 - 93
  • [10] A techno-economic comparison of a direct expansion ground-source and a secondary loop ground-coupled heat pump system for cooling in a residential building
    Guo, Yonghui
    Zhang, Guoqiang
    Zhou, Jin
    Wu, Jiasheng
    Shen, Wei
    [J]. APPLIED THERMAL ENGINEERING, 2012, 35 : 29 - 39