Investigation of the Evaluation of the PD Severity and Verification of the Sensitivity of Partial-Discharge Detection Using the UHF Method in GIS

被引:39
|
作者
Gao, Wensheng [1 ]
Ding, Dengwei [1 ]
Liu, Weidong [1 ]
Huang, Xinhong [2 ]
机构
[1] Tsinghua Univ, Dept Elect Engn, State Key Lab Control & Simulat Power Syst & Gene, Beijing 100084, Peoples R China
[2] Univ Western Ontario, Dept Elect & Comp Engn, London, ON N6A 5B9, Canada
关键词
Evaluation of severity; gas-insulated switchgear (GIS); IEC60270; partial discharge (PD); ultra-high frequency (UHF) method; verification of sensitivity; GAS-INSULATED SUBSTATIONS;
D O I
10.1109/TPWRD.2013.2242206
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
The measurement of partial discharge (PD) using ultra-high frequency (UHF) method is considered an effective approach to monitor the online condition of the equipment, which is used to facilitate the detection of incipient defects in gas-insulated switchgear (GIS). In this paper, in order to assess the severity of PD defects using UHF method, the actual 220-kV GIS were subjected to experimentation. The PD was measured simultaneously by using the UHF method and the IEC60270 measurement technique. The combined measurement has been carried out on different defects in PD test cells, including the floating metal, metallic protrusion, and void in epoxy resin. The inner coupler installed in the GIS tank, and the outer coupler placed outside the spacer, are used to measure the UHF signal. The relationship of the apparent charge and the amplitude of the time-domain signal, and the integral energy from 300 MHz to 1.6 GHz of the signal induced by PD in GIS are analyzed thoroughly. In this way, the severity of PD can be quantified using the UHF signal. In addition, to verify the sensitivity of the UHF detection method, a pulse generator with a rise time of about 500 ps is designed. The GIGRE method for the verification of sensitivity, which is used worldwide, is applied in the experiment. The results of the pulse generator experiment are compared to the results produced by the actual discharge sources, and several possible approaches of improving this method are proposed.
引用
收藏
页码:38 / 47
页数:10
相关论文
共 50 条
  • [1] Improving the Sensitivity Verification Method of the UHF PD Detection Technique for GIS
    Ito, Takashi
    Kamei, Mitsuhito
    Ueta, Genyo
    Okabe, Shigemitsu
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2011, 18 (06) : 1847 - 1853
  • [2] UHF Partial Discharge Detection System for GIS: Application Guide for Sensitivity Verification
    Schichler, U.
    Koltunowicz, W.
    Gautschi, D.
    Girodet, A.
    Hama, H.
    Juhre, K.
    Lopez-Roldan, J.
    Okabe, S.
    Neuhold, S.
    Neumann, C.
    Pearson, J.
    Pietsch, R.
    Riechert, U.
    Tenbohlen, S.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (03) : 1313 - 1321
  • [3] UHF detection method for partial discharge in GIS
    Tagawa, Y
    Takahashi, Y
    Yamagiwa, T
    [J]. JOINT CONFERENCE OF 96' AICDEI / 4T-JCCEID, 1996, : 361 - 364
  • [4] Investigation of Partial Discharge on Typical Defects with UHF Detection Method for GIS
    Tang, Ju
    Tao, Jiagui
    Zhang, Xiaoxing
    Zhou, Jiabin
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2012, 88 (12A): : 351 - 355
  • [5] Research on the Typical Partial Discharge Using the UHF Detection Method for GIS
    Gao, Wensheng
    Ding, Dengwei
    Liu, Weidong
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2011, 26 (04) : 2621 - 2629
  • [6] Sensitivity of the UHF-method for defects in GIS with regard to on-line partial discharge detection
    Kurrer, R
    Klunzinger, K
    Feser, K
    deKock, N
    Sologuren, D
    [J]. CONFERENCE RECORD OF THE 1996 IEEE INTERNATIONAL SYMPOSIUM ON ELECTRICAL INSULATION, VOLS 1 AND 2, 1996, : 95 - 98
  • [7] Severity Evaluation of UHF Signals of Partial Discharge in GIS Based on Semantic Analysis
    Meng, Xianglin
    Song, Hui
    Dai, Jiejie
    Luo, Lingen
    Sheng, Gehao
    Jiang, Xiuchen
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2022, 37 (03) : 1456 - 1464
  • [8] A unique sensitivity verification combined with real-time partial-discharge identification method
    Hoshino, T
    Maruyama, S
    Nojima, K
    Hanai, M
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 2005, 20 (03) : 1890 - 1896
  • [9] Investigation of Disc-type Sensors Using the UHF Method to Detect Partial Discharge in GIS
    Xu, Yang
    Liu, Weidong
    Gao, Wensheng
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2015, 22 (05) : 3019 - 3027
  • [10] Some possible new applications of a partial-discharge (PD) model and its relation to PD-detection sensitivity