Dynamics Characteristics of an Indirect District Heating System and Operational Optimization

被引:0
|
作者
Zhao, Lei [1 ]
Wang, Jia [1 ]
Zhu, Lidong [1 ]
Li, Lianzhong [2 ]
机构
[1] Xian Univ Architecture & Technol, 13 Yanta Rd, Xian 710055, Shaanxi, Peoples R China
[2] Danfoss Automat Controls Management Co Ltd, Shanghai, Peoples R China
来源
PROCEEDINGS OF THE 8TH INTERNATIONAL SYMPOSIUM ON HEATING, VENTILATION AND AIR CONDITIONING, VOL 2: HVAC&R COMPONENT AND ENERGY SYSTEM | 2014年 / 262卷
关键词
District heating system; Dynamic modeling; Control strategy; Operational performance;
D O I
10.1007/978-3-642-39581-9_38
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Based on energy conservation principle and heat transfer mechanisms, a set of dynamic model was established for an indirect district heating system. Dynamic start-up process under ideal condition was simulated and the influence of heat loss from piping network, make-up water and intermediate heat exchange station, and radiator area surplus on the dynamic characteristics of the system was discussed. Dynamic process without control was simulated under the hourly outdoor temperature measured in the days from February 13 to 19, 2012. To overcome the obvious indoor temperature variation with outdoor temperature, four PI control strategies were proposed. The dynamic characteristic and energy consumption of the system operated under these four control strategies were discussed. It is found that the control strategy 3, controlling the fuel flow rate, and water flow rate in the first loop not only produce stable working performance but also obtain considerable energy saving potentials. These results are very helpful to realize the dynamic characteristics of the indirect district heating system and to select suitable control strategy and optimal performance.
引用
收藏
页码:369 / 380
页数:12
相关论文
共 50 条
  • [1] OPERATIONAL OPTIMIZATION IN A DISTRICT-HEATING SYSTEM
    BENONYSSON, A
    BOHM, B
    RAVN, HF
    ENERGY CONVERSION AND MANAGEMENT, 1995, 36 (05) : 297 - 314
  • [2] Operational optimization and algorithm of Hot-Water district heating system
    Zhou, Shoujun
    Zhao, Youen
    Zhang, Congju
    Zhang, Linhua
    ICIC Express Letters, 2015, 9 (05): : 1519 - 1524
  • [3] Operational optimization of district heating system based on an integrated model in TRNSYS
    Lu, Menglong
    Zhang, Chao
    Zhang, Dayu
    Wang, Ruixin
    Zhou, Zhigang
    Zhan, Changhong
    Zai, Xiang
    Jing, Qiang
    ENERGY AND BUILDINGS, 2021, 230
  • [4] Operational optimization of district-heating system based on nonlinear programming algorithm
    Key Laboratory of Renewable Energy Utilization Technologies in Buildings, Ministry of Education, China
    不详
    不详
    ICIC Express Lett Part B Appl., 5 (1369-1373):
  • [5] OPERATIONAL CHARACTERISTICS OF THE COMBINED HEAT AND POWER PLANT IN THE DISTRICT HEATING SYSTEM OF BELGRADE
    Tanasic, Vladimir D.
    Tanasic, Nikola D.
    Stamenic, Mirjana S.
    THERMAL SCIENCE, 2024, 28 (01): : 589 - 597
  • [6] EXAMINATION OF OPERATIONAL OPTIMIZATION AT KEMI DISTRICT HEATING NETWORK
    Ikonen, Enso
    Selek, Istvan
    Kovacs, Jeno
    Neuvonen, Markus
    THERMAL SCIENCE, 2016, 20 (02): : 667 - 678
  • [7] A Transient Thermodynamic Model of District Heating Network for Operational Optimization of the Energy Integration System
    Yao, Shuai
    Gu, Wei
    Lu, Shuai
    Wu, Chenyu
    2017 IEEE CONFERENCE ON ENERGY INTERNET AND ENERGY SYSTEM INTEGRATION (EI2), 2017,
  • [8] Operational optimization of district heating systems with temperature limited sources
    van der Zwan, Sam
    Pothof, Ivo
    ENERGY AND BUILDINGS, 2020, 226
  • [9] Dynamic characteristics and energy consumptions of an indirect district heating system operating in different control strategies
    Zhao, Qingliang
    Zhao, Lei
    Lianzhong
    8TH INTERNATIONAL COLD CLIMATE HVAC CONFERENCE, 2016, 146 : 374 - 378
  • [10] Operational optimization in district heating systems with the use of thermal energy storage
    Lesko, Michal
    Bujalski, Wojciech
    Futyma, Kamil
    ENERGY, 2018, 165 : 902 - 915