Differences in temperature measurement by commercial room temperature sensors: Effects of room cooling system, loads, sensor type and position

被引:11
|
作者
Shinoda, Jun [1 ,2 ]
Mylonas, Angelos [2 ]
Kazanci, Ongun B. [2 ]
Tanabe, Shin-ichi [1 ]
Olesen, Bjarne W. [2 ]
机构
[1] Waseda Univ, Dept Architecture, Shinjuku Ku, 3-4-1 Okubo, Tokyo 1698555, Japan
[2] Tech Univ Denmark, Int Ctr Indoor Environm & Energy, Dept Civil Engn, DK-2800 Lyngby, Denmark
基金
日本学术振兴会;
关键词
Wireless temperature sensor; Wired temperature sensor; Building management system; Thermostat; Radiant cooling; All-air system; INDOOR ENVIRONMENT; THERMAL ENVIRONMENT; HUMAN COMFORT; THERMOSTAT; OFFICES;
D O I
10.1016/j.enbuild.2020.110630
中图分类号
TU [建筑科学];
学科分类号
0813 ;
摘要
Thermostats control the heating, ventilation and air-conditioning (HVAC) system of a building based on the temperature they measure. Integration with communication network technologies allows wireless sensors to be used as the temperature sensing component of an HVAC system, increasing the flexibility in the selection and positioning of sensors. This study compared the temperature measuring performance of nine wireless and two conventional wired temperature sensors against reference air and globe temperature sensors in a climate chamber with a two-person office setup. The influence of sensor position, room cooling system (all-air or radiant with ventilation) and cooling load (33, 61 Wf/m(2)) was studied. Sensors placed at the same position had a measurement difference of up to 1.8 K, and assumptions about the type of temperature a sensor measures (air or globe) had the largest impact on the deviation from the reference temperatures. As opposed to common assumptions, conventional wired temperature sensors measured closer to globe temperature sensors and could be a possible indicator for the operative temperature. When the load settings were high, measurements in radiant system cases had smaller deviations from the reference sensors compared with all-air systems, due to the chilled surface compensating for the radiation from the loads. (C) 2020 Elsevier B.V. All rights reserved.
引用
收藏
页数:12
相关论文
共 50 条
  • [1] Calibration of Room Temperature Magnetic Sensor Array for Biomagnetic Measurement
    Adachi, Yoshiaki
    Oyama, Daisuke
    Terazono, Yasushi
    Hayashi, Tatsuya
    Shibuya, Tomohiko
    Kawabata, Shigenori
    IEEE TRANSACTIONS ON MAGNETICS, 2019, 55 (07)
  • [2] Performance Assessment of a Near Room Temperature Magnetic Cooling System
    Ekren, O.
    Yilanci, A.
    Ezan, M. A.
    Kara, M.
    Biyik, E.
    3RD INTERNATIONAL CONFERENCE ON ENERGY AND ENVIRONMENT RESEARCH, ICEER 2016, 2017, 107 : 188 - 192
  • [3] Ballistic effects up to room temperature in microscopic Hall sensors
    Jouault, B.
    Desrat, W.
    Couturaud, O.
    Contreras, S.
    Mailly, D.
    Mosser, V.
    Zawadzki, W.
    JOURNAL OF APPLIED PHYSICS, 2009, 105 (07)
  • [4] Ballistic effects up to room temperature in microscopic Hall sensors
    Jouault, B.
    Desrat, W.
    Couturaud, O.
    Contreras, S.
    Mailly, D.
    Mosser, V.
    Zawadzki, W.
    Journal of Applied Physics, 2009, 105 (07):
  • [5] Soft-Sensor Modeling of Temperature Variation in a Room under Cooling Conditions
    Xu, Feng
    Sakurai, Kei
    Sato, Yuki
    Sakai, Yuka
    Sabu, Shunsuke
    Kanayama, Hiroaki
    Satou, Daisuke
    Kansha, Yasuki
    ENERGIES, 2023, 16 (06)
  • [6] Numerical analysis of a near-room-temperature magnetic cooling system
    Ezan, Mehmet Akif
    Ekren, Orhan
    Metin, Cagri
    Yilanci, Ahmet
    Biyik, Emrah
    Kara, Salih Murat
    INTERNATIONAL JOURNAL OF REFRIGERATION-REVUE INTERNATIONALE DU FROID, 2017, 75 : 262 - 275
  • [7] A pre-industrial magnetic cooling system for room temperature application
    Balli, M.
    Sari, O.
    Mahmed, C.
    Besson, Ch.
    Bonhote, Ph.
    Duc, D.
    Forchelet, J.
    APPLIED ENERGY, 2012, 98 : 556 - 561
  • [8] The Effects of Cooling Rate on Deformation Mechanism at Room Temperature in Mild Steel
    Kim, SungSoo
    Lee, Yoon Sang
    Kim, Young Suk
    KOREAN JOURNAL OF METALS AND MATERIALS, 2016, 54 (12): : 875 - 884
  • [9] A Novel Type Room Temperature Surface Photovoltage Gas Sensor Device
    Kwoka, Monika
    Borysiewicz, Michal A.
    Tomkiewicz, Pawel
    Piotrowska, Anna
    Szuber, Jacek
    SENSORS, 2018, 18 (09)
  • [10] Research on Calibration Method of Infrared Temperature Measurement System Near Room Temperature Field
    Cui, Shuanglong
    Xing, Jian
    FRONTIERS IN PHYSICS, 2022, 9