Microgrid dynamic response during the pre-planned and forced islanding processes involving DFIG and synchronous generators

被引:11
|
作者
Vasquez-Arnez, Ricardo Leon [1 ]
Ramos, Dorel Soares [2 ]
Del Carpio-Huayllas, Tesoro Elena [2 ]
机构
[1] Fdn Technol Dev Engn Sci, BR-05615010 Sao Paulo, Brazil
[2] Univ Sao Paulo, Elect Power & Automat Engn Dept, BR-05508900 Sao Paulo, Brazil
关键词
DFIG generator; Forced islanding; Load shedding; Microgrid systems; Pre-planned islanding; STABILITY;
D O I
10.1016/j.ijepes.2014.04.044
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
In this article, some important issues associated to the dynamic response of a microgrid system are addressed. In particular, issues related to the pre-planned islanding mode of operation, load shedding, loss of one generator and the failure to shed an unforeseen connected load are studied. In this context, the dynamic behavior results of a Doubly-Fed Induction Generator (DFIG) and two other synchronous sources (a diesel and a small hydro-generator) within a microgrid, are presented. The overloading condition can occur due to causes ranging from poor load schedule, inadequate switching of circuits within the microgrid, illegal connection of load by some low voltage consumers, etc. In most of the simulated conditions the microgrid generators resumed their operation after clearing the disturbance. However, under some critical conditions, like in the case of a considerably large load connected, the microgrid was unable to return to the pre-fault condition and even failed while trying to gain stability for this new load condition. Because microgrid systems normally have low equivalent inertia, it was also observed that very little to practically no overload can be accepted by the generators. (C) 2014 Elsevier Ltd. All rights reserved.
引用
收藏
页码:175 / 182
页数:8
相关论文
empty
未找到相关数据