Conventional and advanced exergy analyses of an air-conditioning system in a subway station

被引:5
|
作者
Yin, Hua [1 ,2 ]
Guo, Huafang [1 ,2 ]
Tang, Zhihua [1 ,2 ]
Yu, Junyan [3 ]
Lu, Haiyang [4 ]
机构
[1] Chinese Acad Sci, Guangzhou Inst Energy Convers, Key Lab Renewable Energy, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China
[2] Guangdong Key Lab New & Renewable Energy Res & De, 2 Nengyuan Rd, Guangzhou 510640, Guangdong, Peoples R China
[3] Guangzhou Metro Grp Co Ltd, Tower A,Wansheng Sq,1238 Xingang East Rd, Guangzhou 510330, Guangdong, Peoples R China
[4] Guangdong Univ Technol, Sch Automated Inst, Waihuan West Rd, Guangzhou 5100006, Guangdong, Peoples R China
关键词
conventional and advanced exergy analyses; air-conditioning system; subway station; CARBON-DIOXIDE; ENERGY; DESTRUCTIONS; OPTIMIZATION; PLANT; CYCLE; HVAC;
D O I
10.1504/IJEX.2019.100365
中图分类号
O414.1 [热力学];
学科分类号
摘要
Air-conditioning systems in subway stations consume a large amount of energy. In this study, conventional and advanced exergy analyses were carried out to determine the energy-saving potential of an air-conditioning system in a subway station. Results show that air handling unit (AHU) should be improved for the highest values of relative irreversibility (RI) with conventional exergy analysis, whereas the compressor should have the highest improvement priority for the largest avoidable exergy destruction with advanced exergy analysis. Moreover, influences of compressor efficiency, condensation temperature, and evaporation temperature on avoidable exergy destruction of the air-conditioning system were also investigated. According to the findings, compressor efficiency significantly influences the system's total avoidable exergy destruction. The lower the compressor efficiency, the more rapidly the avoidable exergy destruction of the compressor increases. Furthermore, the avoidable exergy destruction of condenser, compressor, cooling tower (CT), and cooling water pump (CWP) increases with the rise of the condensation temperature, whereas that of the evaporator, throttling valve (TV), condenser, compressor, CT, and CWP decreases with the rise of the evaporation temperature.
引用
收藏
页码:236 / 262
页数:27
相关论文
共 50 条
  • [1] Exergy and Thermoeconomic Analysis for an Underground Train Station Air-Conditioning Cooling System
    Liao, Ke Yang
    Chuah, Yew Khoy
    [J]. ENTROPY, 2016, 18 (03)
  • [2] Research on Subway Air-Conditioning System Design
    Chai, Zhi
    Nan, Jinrui
    Huang, Junkui
    [J]. INFORMATION TECHNOLOGY APPLICATIONS IN INDUSTRY II, PTS 1-4, 2013, 411-414 : 3039 - 3045
  • [3] Measurement analysis and load characteristics research on subway station ventilation and air-conditioning system
    Liu, Zhengning
    Wang, Wenqiang
    Sun, Chunhui
    [J]. Journal of Railway Science and Engineering, 2024, 21 (11) : 4746 - 4755
  • [4] NUMERICAL PREDICTION OF AIR DISTRIBUTION OF VENTILATION AND AIR-CONDITIONING IN A SUBWAY TRANSFER STATION
    He, Kaiyuan
    Fan, Hongming
    Wang, Feng
    Zhao, Yaohua
    Yin, Zhifang
    [J]. FIFTH INTERNATIONAL WORKSHOP ON ENERGY AND ENVIRONMENT OF RESIDENTIAL BUILDINGS AND THIRD INTERNATIONAL CONFERENCE ON BUILT ENVIRONMENT AND PUBLIC HEALTH, VOL I AND II, PROCEEDINGS, 2009, : 533 - 540
  • [5] Exergy and entransy analyses in air-conditioning system part 1-Similarity and distinction
    Zhang, Tao
    Liu, Xiaohua
    Tang, Haida
    Liu, Jun
    Jiang, Yi
    [J]. ENERGY AND BUILDINGS, 2016, 128 : 876 - 885
  • [6] Study on Dynamic Load of Air-Conditioning System in Subway Station Based on Hourly Passenger Flow
    Wang, Liang
    Li, Yangli
    Deng, Shudan
    Zhao, Juan
    [J]. BUILDINGS, 2023, 13 (09)
  • [7] Exergy and entransy analyses in air-conditioning system part 2-Humid air handling process
    Zhang, Tao
    Liu, Xiaohua
    Liu, Jun
    Tang, Haida
    Jiang, Yi
    [J]. ENERGY AND BUILDINGS, 2017, 139 : 10 - 21
  • [8] Operating optimization of air-conditioning water system in a subway station using data mining and dynamic system models
    Su, Xing
    Huang, Yixiang
    Wang, Lei
    Tian, Shaochen
    Luo, Yanping
    [J]. JOURNAL OF BUILDING ENGINEERING, 2021, 44
  • [9] Conventional and advanced exergy analyses of an underwater compressed air energy storage system
    Wang, Zhiwen
    Xiong, Wei
    Ting, David S. -K.
    Carriveau, Rupp
    Wang, Zuwen
    [J]. APPLIED ENERGY, 2016, 180 : 810 - 822
  • [10] Time-delay characteristics of air-conditioning system for subway trains
    Zhou, Yuanlong
    Bi, Haiquan
    Wang, Honglin
    Zhao, Yichen
    Lei, Bo
    [J]. JOURNAL OF BUILDING ENGINEERING, 2021, 40