Analysis of a short-circuit ring impact problem and design of a new ventilator for a 625 kVA generator, using SVL

被引:0
|
作者
Oslinger, Jose L. [1 ]
Palacios, Jairo A. [1 ]
Jaramillo, Guillermo A. [1 ]
机构
[1] Univ Valle, Valle, Colombia
关键词
simplified virtual laboratory; finite element analysis; computational fluid dynamics; electrical machines;
D O I
10.1016/j.matcom.2006.02.023
中图分类号
TP39 [计算机的应用];
学科分类号
081203 ; 0835 ;
摘要
The necessity of an energy supplier was to solve an impact problem presented at the damper winding ring or short-circuit ring of a 625 kVA generator and to redesign a fan for it. The principal restriction was the time. It should be done in 15 calendar days, working with drawings of the machine, operational data and from specifications, taking measures from the real machine during just one day while the machine's maintenance began in order to solve the impact problem which real cause was not found yet. The answer was found working with the concept of simplified virtual laboratory (SVL) using finite elements analysis (FEA) and failure analysis from visual inspection. A fast and effective method which combines simplified 2D computational fluid dynamics (CID) Models and analytical formulation from electrical machines bibliography allowing time and money saving is shown. (c) 2006 IMACS. Published by Elsevier B.V. All rights reserved.
引用
收藏
页码:282 / 289
页数:8
相关论文
共 5 条
  • [1] Design and Short-Circuit Analysis of a 1 MW Superconducting Generator for Electric Aircraft
    Wang, Yihan
    Liu, Yuwei
    Zhou, Linjie
    Yuan, Qi
    Song, Xiaowei
    Li, Liang
    Wang, Qiuliang
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2025, 35 (05)
  • [2] Analysis and Design of a New Ring Bandstop Filter Using Lumped Equivalent Circuit
    Yang, Chaoyue
    Fu, Chengfang
    PROGRESS IN ELECTROMAGNETICS RESEARCH LETTERS, 2020, 93 : 81 - 87
  • [3] Analysis and design of a new ring bandstop filter using lumped equivalent circuit
    Yang, Chaoyue
    Fu, Chengfang
    Progress in Electromagnetics Research Letters, 2020, 93 : 81 - 87
  • [4] Analysis of Air-Gap Influence on a Large Hydro Generator's Parameters Using Sudden Symmetrical Short-Circuit Test
    Kokoko, O.
    Merkhouf, A.
    Tounzi, A.
    Al-Haddad, K.
    Guillot, E.
    2015 IEEE INTERNATIONAL ELECTRIC MACHINES & DRIVES CONFERENCE (IEMDC), 2015, : 102 - 107
  • [5] NEW METHOD OF ANALYSIS FOR THE ERROR DUE TO SPECTRAL MISMATCH IN SHORT-CIRCUIT CURRENT MEASUREMENT USING THE REFERENCE SOLAR-CELL METHOD
    SHIMOKAWA, R
    HORIGUCHI, M
    HAMAKAWA, Y
    SOLAR CELLS, 1985, 13 (03): : 221 - 230