Partial Discharge Behavior and Ground Insulation Life Expectancy Under Different Voltage Frequencies

被引:58
|
作者
Liu, Tao [1 ]
Li, Qingmin [1 ]
Huang, Xuwei [1 ]
Lu, Yangfei [1 ]
Asif, Muhammad [1 ]
Wang, Zhongdong [2 ]
机构
[1] North China Elect Power Univ, State Key Lab Alternate Elect Power Syst Renewabl, Beijing 102206, Peoples R China
[2] Univ Manchester, Sch Elect & Elect Engn, Manchester M13 9PL, Lancs, England
基金
中国国家自然科学基金;
关键词
Partial discharges; insulation life; voltage frequency; high-frequency insulation; polyimide; ELECTRICAL INSULATION; CHARGE ACCUMULATION; DEGRADATION; PD;
D O I
10.1109/TDEI.2018.006810
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Power electronic transformers, namely solid state transformers, have aroused a widespread attention due to the integration issue of large scale renewable energy in modern power system. High frequency power transformer (HFPT) is one of its key components operating at several to tens of kHz. Under such high frequency voltage, accelerated insulation aging and premature insulation failure occur frequently. Partial discharge (PD) is considered as the main cause of electrical performance deterioration in HV systems or LV ones where overvoltage or surge may occur. Therefore, it is necessary to study the PD behavior and insulation life under different voltage frequencies, in order to have a better understanding of premature failure mechanism. In this paper frequency dependence of space charge and PD properties is firstly analyzed theoretically and mathematically, followed by the results of electrical aging tests conducted on polyimide (PI) films that were subjected to surface PDs under 5-30 kHz sinusoidal voltage. Discharge characteristics and lifetime of PI film under different frequencies have been discussed, along with the correlation between lifetime and PD. Both theoretical analyses and experimental results show that average PD amplitude and total PD number per cycle increase first and then decrease afterwards with voltage frequency, which means that the frequency induced inflection phenomenon exists in the tested frequency range. Synergistic action of high frequency induced thermal effect and reduced space charge dissipation time under high frequency is the reason for this novel phenomenon. Besides, strong linear correlation has been found between lifetime and PD characteristic total PD amplitude per second, which reveals the accelerated aging mechanism under high frequency electrical stress.
引用
收藏
页码:603 / 613
页数:11
相关论文
共 50 条
  • [1] Characteristics of partial discharge in oil impregnated insulation using different test voltage frequencies
    Ariastina, WG
    Blackburn, TR
    PROCEEDINGS OF THE 6TH INTERNATIONAL CONFERENCE ON PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS, VOLS 1 & 2, 2000, : 487 - 492
  • [2] Effect of Voltage Waveform on Partial Discharge Characteristics and Insulation Life
    Dong, Guojing
    Liu, Tao
    Zhang, Minhao
    Li, Qingmin
    Wang, Zhongdong
    2018 12TH INTERNATIONAL CONFERENCE ON THE PROPERTIES AND APPLICATIONS OF DIELECTRIC MATERIALS (ICPADM 2018), 2018, : 144 - 147
  • [3] Partial discharge detection using oscillating voltage at different frequencies
    Morshuis, PHF
    Bodega, R
    Lazzaroni, M
    Wester, FJ
    IMTC 2002: PROCEEDINGS OF THE 19TH IEEE INSTRUMENTATION AND MEASUREMENT TECHNOLOGY CONFERENCE, VOLS 1 & 2, 2002, : 431 - 435
  • [4] Insulation life model and partial discharge characteristic of magnet wires under square pulse voltage
    School of Electrical Engineering, Southwest Jiaotong University, Chengdu 610031, China
    不详
    Xinan Jiaotong Daxue Xuebao, 2012, 6 (1009-1014):
  • [5] Partial discharge inception voltage in PCB defect samples under different frequencies of alternating sine wave voltage
    Chang, Chien-Kuo
    Lyu, Chong-Yi
    Tsai, Hua-Wen
    Boyanapalli, Bharath Kumar
    ENGINEERING RESEARCH EXPRESS, 2025, 7 (01):
  • [6] Study on Characteristics of Partial Discharge in XLPE Cable under Damped AC Voltage at Different Frequencies
    Yu, Peixiang
    Zhang, Long
    Li, Ruipeng
    Yang, Yuqi
    Li, Hongjie
    MODERN TECHNOLOGIES IN MATERIALS, MECHANICS AND INTELLIGENT SYSTEMS, 2014, 1049 : 750 - +
  • [7] Partial discharge activity of inter-turn insulation under different parameters of square wave voltage
    Zhou, Kai
    Wu, Guangning
    Guo, Xiaoxia
    Zhou, Liren
    Zhang, Tao
    IEEJ Transactions on Fundamentals and Materials, 2009, 129 (12) : 922 - 930
  • [8] Partial Discharge Measurements in XLPE Cables with Misplaced Grading System Under Different Applied Voltage Frequencies
    Setyowibowo, Arief
    Suwarno
    Cavallini, Andrea
    Montanan, Gian Carlo
    2017 INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND POWER SYSTEMS (ICHVEPS), 2017, : 460 - 465
  • [9] Partial Discharge Patterns in High Voltage Insulation
    Illias, Hazlee
    Yuan, Teo Soon
    Abu Bakar, Ab Halim
    Mokhlis, Hazlie
    Chen, George
    Lewin, Paul L.
    2012 IEEE INTERNATIONAL CONFERENCE ON POWER AND ENERGY (PECON), 2012, : 750 - 755
  • [10] The Effect of Inverter Characteristics on Partial Discharge and Life Behavior of Wire Insulation
    Montanari, Gian Carlo
    Seri, Paolo
    IEEE ELECTRICAL INSULATION MAGAZINE, 2018, 34 (02) : 32 - 39