Reduction of Electromagnetic Force in AC Distributed Winding of Fault Current Limiter under Short-Circuit Condition

被引:2
|
作者
Ghabeli, Asef [1 ]
Yazdani-Asrami, Mohammad [1 ]
Doroudi, Aref [2 ]
Gholamian, S. Asghar [3 ]
机构
[1] Islamic Azad Univ, Sari Branch, Young Researchers & Elite Club, Sari, Iran
[2] Shahed Univ, Fac Elect Engn, Shahed, Iran
[3] Babol Univ Technol, Fac Elect & Comp Engn, Elect Machinery Lab, Babol Sar, Iran
关键词
fault current limiter; short-circuit current; fmite element method; electromagnetic force; FIELD;
D O I
10.4283/JMAG.2015.20.4.400
中图分类号
T [工业技术];
学科分类号
08 ;
摘要
Various kinds of winding arrangements can be used to enable fault current limiters (FCL) to tolerate higher forces without resulting in a substantial increase in construction and fabrication costs. In this paper, a distributed winding arrangement is investigated in terms of its effects on the short-circuit forces in a three-phase FCL. The force magnitudes of the AC supplied windings are calculated by employing a fmite element-based model in the time stepping procedure. The leakage flux and radial and axial force magnitudes obtained from the simulation are compared to those obtained from a conventional winding arrangement; The comparison shows that the distributed winding arrangement significantly reduces the radial and, especially, the axial force magnitudes.
引用
收藏
页码:400 / 404
页数:5
相关论文
共 50 条
  • [1] AC distributed power supplies used for solid state short-circuit fault current limiter
    Wen Huiqing
    Wen Xuhui
    Lu Zhengyu
    2007 INTERNATIONAL CONFERENCE ON ELECTRICAL MACHINES AND SYSTEMS, VOLS 1-4, 2007, : 879 - 883
  • [2] Electromagnetic Environment of 750 kV Economical Fault Current Limiter Under Power Frequency Short-circuit
    Hou D.
    Liu J.
    Liu C.
    Zou J.
    Gaodianya Jishu/High Voltage Engineering, 2022, 48 (11): : 4638 - 4646
  • [3] Analysis of Electromagnetic Forces in Superconducting Fault-Current Limiters Under Short-Circuit Condition
    Vilhena, Nuno
    Taillacq, Amanda
    Pronto, Anabela
    Murta-Pina, Joao
    Alvarez, Alfredo
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2016, 26 (03)
  • [4] Electromagnetic Force Analysis of a Power Transformer Under the Short-Circuit Condition
    Li, Yi
    Xu, Qiuyuan
    Lu, Yanfeng
    IEEE TRANSACTIONS ON APPLIED SUPERCONDUCTIVITY, 2021, 31 (08)
  • [5] Short-circuit current difference of parallel strands in winding turns and its influence on the distribution of electromagnetic force
    Zhao, Yi
    Si, Jian
    Jin, Mingkai
    Wen, Tao
    Guo, Penghong
    Chen, Weijiang
    IET ELECTRIC POWER APPLICATIONS, 2023, 17 (12) : 1562 - 1572
  • [6] Using the fault current limiter with spark gap to reduce short-circuit currents
    Zhang Xiaoqing
    Ming Li
    IEEE TRANSACTIONS ON POWER DELIVERY, 2008, 23 (01) : 506 - 507
  • [7] Short-Circuit Electromagnetic Force Distribution Characteristics in Transformer Winding Transposition Structures
    Zhao, Yi
    Chen, Weijiang
    Jin, Mingkai
    Wen, Tao
    Xue, Jiyin
    Zhang, Qiaogen
    Chen, Ming
    IEEE TRANSACTIONS ON MAGNETICS, 2020, 56 (12)
  • [8] Reliability Enhancement of Power IGBTs under Short-Circuit Fault Condition Using Short-Circuit Current Limiting-Based Technique
    Mohsenzade, Sadegh
    Naghibi, Javad
    Mehran, Kamyar
    ENERGIES, 2021, 14 (21)
  • [9] A study on effect of fault current limiter on bus voltage sag during short-circuit fault
    Polytechnic University, 4-1-1, Hashimotodai, Sagamihara 229-1196, Japan
    不详
    IEEJ Trans. Power Energy, 2008, 2 (486-492+15):
  • [10] SHORT CIRCUIT CURRENT LIMITER IN AC NETWORK
    吴兆麟
    谌平平
    谭凌云
    江道灼
    Journal of Zhejiang University Science, 2001, (01) : 42 - 46