Thermodynamic analysis of the optimal operating conditions for a two-stage CO2 refrigeration unit in warm climates with and without ejector

被引:21
|
作者
Antonio Exposito-Carrillo, Jose [1 ]
Jose Sanchez-de La Flor, Francisco [1 ]
Peris-Perez, Bernardo [2 ]
Manuel Salmeron-Lissen, Jose [2 ]
机构
[1] Univ Cadiz, Dept Maquinas & Motores Term, Escuela Super Ingn, Avda Univ Cadiz, Puerto Real 11519, Spain
[2] Univ Seville, Grp Termotecnia, Escuela Tecn Super Ingn, Camino Descubrimientos S-N, Seville 41092, Spain
关键词
Refrigeration; R744; Ejector; Operating conditions; Optimisation; ENERGY EFFICIENCY; SYSTEM; PLANT; SUPERMARKETS; PROTOTYPE; WORKING; FUTURE;
D O I
10.1016/j.applthermaleng.2020.116284
中图分类号
O414.1 [热力学];
学科分类号
摘要
The natural refrigerant R744 seems to be the long term solution to be imposed in the food retail industry, where low and medium refrigeration temperatures are usually required, despite the technical difficulties related to high the pressure, especially in warm climates, leading to trans-critical operation with the consequent COP reduction. To overcome such difficulties, different approaches have been proposed in literature, being very popular the use of parallel compressor or its combination with ejector expansion devices. The efficient operation of trans-critical R744 systems requires the control of the gas cooler pressure, as well as the pressure of the flash-tank. In the case of ejector expansion devices, the ratio of entrained mass flow rate must be also included in the control variables and, at the same time, its use implies additional restrictions. The current paper presents the optimization methodology for the operating conditions of a two-stage CO2 refrigeration unit for both cases, with and without ejector. The curves of optimal combinations of gas cooler and flash-tank pressures, understood as operational control laws, are provided together with the COP achieved. The operating conditions and performance of the ejector case are compared showing COP improvements of up to 13%. The results also show that the operating region of the control variables is limited due to the use of the ejector.
引用
收藏
页数:14
相关论文
共 50 条
  • [1] Thermodynamic analysis of a modified transcritical CO2 two-stage compression dual-temperature refrigeration cycle with an ejector
    Wen, Zhidong
    Bai, Tao
    Wan, Jiahao
    [J]. APPLIED THERMAL ENGINEERING, 2024, 257
  • [2] Thermodynamic analysis of hybrid two-stage CO2 mechanical compression–ejector cooling cycle
    Volodymyr Ierin
    Guangming Chen
    Xinyue Hao
    Oleksii Volovyk
    [J]. International Journal of Air-Conditioning and Refrigeration, 31
  • [3] Thermodynamic study on a new transcritical CO2 ejector expansion refrigeration system with two-stage evaporation and vapor feedback
    He, Yang
    Deng, Jianqiang
    Zhang, Zaoxiao
    [J]. HVAC&R RESEARCH, 2014, 20 (06): : 655 - 664
  • [4] Thermoeconomic analysis of CO2 Ejector-Expansion Refrigeration Cycle (EERC) for low-temperature refrigeration in warm climates
    Peris Perez, Bernardo
    Exposito Carrillo, Jose Antonio
    Sanchez de La Flor, Francisco Jose
    Salmeron Lissen, Jose Manuel
    Morillo Navarro, Andres
    [J]. APPLIED THERMAL ENGINEERING, 2021, 188
  • [5] Thermodynamic analysis of transcritical CO2 refrigeration cycle with an ejector
    Sun Fangtian
    Ma Yitai
    [J]. APPLIED THERMAL ENGINEERING, 2011, 31 (6-7) : 1184 - 1189
  • [6] Thermodynamic analysis of CO2 trans-critical two-stage compression refrigeration cycle
    Key Laboratory of Condition Monitoring and Control of Power Plant Equipment, North China Electric Power University, Baoding 071003, China
    [J]. Huagong Xuebao, 2008, 12 (2985-2989):
  • [7] Thermodynamics analysis of a modified dual-evaporator CO2 transcritical refrigeration cycle with two-stage ejector
    Bai, Tao
    Yan, Gang
    Yu, Jianlin
    [J]. ENERGY, 2015, 84 : 325 - 335
  • [9] Experimental investigation on a transcritical CO2 ejector expansion refrigeration system with two-stage evaporation
    Zheng, Lixing
    Deng, Jianqiang
    [J]. APPLIED THERMAL ENGINEERING, 2017, 125 : 919 - 927
  • [10] Cycle improvements to ejector-expansion transcritical CO2 two-stage refrigeration cycle
    Yari, M.
    Sirousazar, M.
    [J]. INTERNATIONAL JOURNAL OF ENERGY RESEARCH, 2008, 32 (07) : 677 - 687