Variation of Discharge Characteristics With Temperature in Moving Transformer Oil Contaminated by Metallic Particles

被引:21
|
作者
Pan, Cheng [1 ]
Tang, Ju [1 ,2 ]
Zhang, Yongze [2 ]
Luo, Xinyu [2 ]
Li, Xingxing [2 ]
机构
[1] Wuhan Univ, Sch Elect Engn, Wuhan 430072, Hubei, Peoples R China
[2] Chongqing Univ, State Key Lab Power Transmiss Equipment & Syst Se, Chongqing 400044, Peoples R China
来源
IEEE ACCESS | 2018年 / 6卷
基金
中国国家自然科学基金; 中国博士后科学基金;
关键词
Temperature; partial discharge; breakdown; moving transformer oil; metallic particles; INSULATING OIL; COMBINED AC; DC; BREAKDOWN; BEHAVIOR;
D O I
10.1109/ACCESS.2018.2856580
中图分类号
TP [自动化技术、计算机技术];
学科分类号
0812 ;
摘要
During the operation of power transformers, the insulating oil is actually in a moving state due to the effects of various cooling systems. Therefore, the investigation on insulation characters of moving transformer oil is necessary. In this paper, the influences of temperature on partial discharge (PD) and breakdown characteristics of moving transformer oil contaminated by metallic particles were experimentally studied at first. It was found that the PD magnitude and frequency first decreased and then became higher when the temperature increased from 40 degrees C to 80 degrees C, and a minimum point appeared between 70 degrees C and 80 degrees C. On the contrary, the dependence of breakdown voltage on temperature showed an opposite tendency. In order to explain the experimental results, a simulation model involving multiple forces was constructed to obtain the movement trajectory of particles. The increase of oil temperature leaded to the decrease of dynamic viscosity of transformer oil, so the forces acting on particles and their movement characters changed. As the temperature increased, the collision frequency between particles and electrodes first decreased and then became higher, and there was a minimum point between 70 degrees C and 80 degrees C. This changing tendency was in accordance with the dependence of PD parameters on the oil temperature. In terms of the above results, the effects of temperature on PD frequency and breakdown voltage were discussed.
引用
收藏
页码:40050 / 40058
页数:9
相关论文
共 50 条
  • [1] Partial Discharge and Breakdown Characteristics of Moving Transformer Oil Contaminated by Metallic Particles
    Pan, Cheng
    Tang, Ju
    Tao, Xiantao
    Zhang, Yongze
    Ma, Shouxiao
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (05) : 1774 - 1784
  • [2] The Impact of Temperature on the Partial Discharge Characteristics of Moving Charged Metal Particles in Transformer Oil
    Li, Xingxing
    Tang, Ju
    Ma, Shouxiao
    Yao, Qiang
    [J]. 2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [3] DC Breakdown Characteristics of Flowing Transformer Oil Contaminated by Metallic Particles
    Yao, Yuhang
    Tao, Xiantao
    Yu, Mengyue
    Pan, Cheng
    Tang, Ju
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2023, 38 : 157 - 167
  • [4] Motion Behaviors and Partial Discharge Characteristics of Metallic Particles in Moving Transformer Oil under AC/DC Composite Voltage
    Yao Y.
    Pan C.
    Tang J.
    Luo X.
    Xia S.
    [J]. Diangong Jishu Xuebao/Transactions of China Electrotechnical Society, 2021, 36 (15): : 3101 - 3112
  • [5] Impact of metal particle size on partial discharge characteristics of moving metal particles in transformer oil
    Ma, Shouxiao
    Yang, Dongmei
    Liang, Bin
    Jin, Ying
    [J]. CHEMICAL PHYSICS LETTERS, 2019, 731
  • [6] Investigations of Partial Discharge Characteristics of Moving Metal Particles in Transformer Oil Flow under AC Voltage
    Gu, Chao
    Zhou, Jiabin
    Tang, Ju
    Luo, Xinyu
    Zhu, Wenbing
    Zhu, Mengzhao
    [J]. 2018 INTERNATIONAL CONFERENCE ON POWER SYSTEM TECHNOLOGY (POWERCON), 2018, : 3383 - 3388
  • [7] Impact of velocity on partial discharge characteristics of moving metal particles in transformer oil using UHF technique
    Tang J.
    Ma S.
    Li X.
    Zhang Y.
    Pan C.
    Su J.
    [J]. 1600, Institute of Electrical and Electronics Engineers Inc., United States (23): : 2207 - 2212
  • [8] Impact of Velocity on Partial Discharge Characteristics of Moving Metal Particles in Transformer Oil using UHF Technique
    Tang, Ju
    Ma, Shouxiao
    Li, Xingxing
    Zhang, Yongze
    Pan, Cheng
    Su, Jinsheng
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2016, 23 (04) : 2207 - 2212
  • [9] BREAKDOWN CHARACTERISTICS OF MOVING TRANSFORMER OIL
    IKEDA, M
    TERANISHI, T
    HONDA, M
    YANARI, T
    [J]. IEEE TRANSACTIONS ON POWER APPARATUS AND SYSTEMS, 1981, 100 (02): : 921 - 928
  • [10] Study on the partial discharge characteristics induced by the motion of cellulose particles in transformer oil
    Liu, Yijin
    Zhao, Tao
    Liu, Yunpeng
    Liu, Yunuo
    Xu, Jiaxue
    Yang, Chaojie
    [J]. IET ELECTRIC POWER APPLICATIONS, 2024, : 1044 - 1055