Cooling performance of a vertical ground-coupled heat pump system installed in a school building

被引:77
|
作者
Hwang, Yujin [2 ]
Lee, Jae-Keun [2 ]
Jeong, Young-Man [2 ]
Koo, Kyung-Min [2 ]
Lee, Dong-Hyuk [3 ]
Kim, In-Kyu [3 ]
Jin, Sim-Won [3 ]
Kim, Soo H. [1 ]
机构
[1] Pusan Natl Univ, Dept Nanosyst & Nanoproc Engn, Pusan 609735, South Korea
[2] Pusan Natl Univ, Dept Mech Engn, Pusan 609735, South Korea
[3] LG Elect, Chang Won, Gyeongnam, South Korea
基金
新加坡国家研究基金会;
关键词
Ground source heat pump; Water-to-refrigerant; Cooling performance; Ground heat exchanger; AIR-SOURCE; DESIGN;
D O I
10.1016/j.renene.2008.05.042
中图分类号
X [环境科学、安全科学];
学科分类号
08 ; 0830 ;
摘要
This paper presents the cooling performance of a water-to-refrigerant type ground heat source heat pump system (GSHP) installed in a school building in Korea. The evaluation of the cooling performance has been conducted under the actual operation of GSHP system in the summer of year 2007. Ten heat pump units with the capacity of 10 HP each were installed in the building. Also, a closed vertical typed-ground heat exchanger with 24 boreholes of 175 m in depth was constructed for the GSHP system. To analyze the cooling performance of the GSHP system, we monitored various operating conditions, including the outdoor temperature, the ground temperature, and the water temperature of inlet and outlet of the ground heat exchanger. Simultaneously, the cooling capacity and the input power were evaluated to determine the cooling performance of the GSHP system. The average cooling coefficient of performance (COP) and overall COP of the GSHP system were found to be similar to 8.3 and similar to 5.9 at 65% partial load condition, respectively. While the air source heat pump (ASHP) system, which has the same capacity with the GSHP system, was found to have the average COP of similar to 3.9 and overall COP of similar to 3.4, implying that the GSHP system is more efficient than the ASHP system due to its lower temperature of condenser. (C) 2008 Elsevier Ltd. All rights reserved.
引用
收藏
页码:578 / 582
页数:5
相关论文
共 50 条
  • [1] The performance improvements of a ground-coupled heat pump system for both building heating and cooling modes
    Qi, Zishu
    Gao, Qing
    Liu, Yan
    Yan, Y. Y.
    Spitler, Jeffrey D.
    [J]. PROGRESS IN POWER AND ELECTRICAL ENGINEERING, PTS 1 AND 2, 2012, 354-355 : 807 - +
  • [2] Seasonal cooling performance of a ground-coupled heat pump system in a hot and and climate
    Inalli, M
    Esen, H
    [J]. RENEWABLE ENERGY, 2005, 30 (09) : 1411 - 1424
  • [3] Heating performance of a ground source heat pump system installed in a school building
    Jaedo Song
    Kwangho Lee
    Youngman Jeong
    Seongir Cheong
    Jaekeun Lee
    Yujin Hwang
    Yeongho Lee
    Donghyuk Lee
    [J]. Science in China Series E: Technological Sciences, 2010, 53 : 80 - 84
  • [4] Heating performance of a ground source heat pump system installed in a school building
    Jaedo SONG
    Kwangho LEE
    Youngman JEONG
    Seongir CHEONG
    Jaekeun LEE
    Yujin HWANG
    Yeongho LEE
    Donghyuk LEE
    [J]. Science China(Technological Sciences), 2010, 53 (01) - 84
  • [5] Heating performance of a ground source heat pump system installed in a school building
    Song, Jaedo
    Lee, Kwangho
    Jeong, Youngman
    Cheong, Seongir
    Lee, Jaekeun
    Hwang, Yujin
    Lee, Yeongho
    Lee, Donghyuk
    [J]. SCIENCE CHINA-TECHNOLOGICAL SCIENCES, 2010, 53 (01) : 80 - 84
  • [6] Heating performance of a ground source heat pump system installed in a school building
    Jaedo SONG
    Kwangho LEE
    Youngman JEONG
    Seongir CHEONG
    Jaekeun LEE
    Yujin HWANG
    Yeongho LEE
    Donghyuk LEE
    [J]. Science China Technological Sciences, 2010, (01) : 80 - 84
  • [7] Optimization and Analysis of a Vertical Ground-Coupled Heat Pump
    Kord, Ali Siavoshi
    Jazayeri, Seyed Ali
    [J]. INTERNATIONAL JOURNAL OF RENEWABLE ENERGY RESEARCH, 2012, 2 (01): : 33 - 37
  • [8] Temperature distributions in boreholes of a vertical ground-coupled heat pump system
    Esen, Hikmet
    Inalli, Mustafa
    Esen, Yuksel
    [J]. RENEWABLE ENERGY, 2009, 34 (12) : 2672 - 2679
  • [9] Experimental study on the cooling operation characteristics of a closed loop vertical ground-coupled heat pump system
    Yang, W. B.
    Liu, G. Y.
    Shi, M. H.
    Chen, Z. Q.
    [J]. CRYOGENICS AND REFRIGERATION, PROCEEDINGS, 2008, : 775 - 779
  • [10] GROUND-COUPLED HEAT-PUMP SYSTEM
    DROWN, DC
    DENBRAVEN, KR
    [J]. ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1992, 34 (08): : 14 - 14