Partial Discharge Measurement and Analysis of Transformer Under Oscillating Lightning Impulse Voltage

被引:0
|
作者
Zhang, Xuanrui [1 ]
Guo, Ruochen [1 ]
Yang, Yun [2 ]
Hu, Yidan [1 ]
Zhang, Zhaoyu [1 ]
Li, Junhao [1 ]
Han, Xutao [1 ]
机构
[1] Xi An Jiao Tong Univ, State Key Lab Elect Insulat & Power Equipment, Xian 710049, Peoples R China
[2] China Southern Power Grid, Natl Engn Lab UHV Technol Kunming, Kunming 650000, Peoples R China
关键词
Disruptive effect (DE) method; field test; oscillating lightning impulse (OLI); partial discharges (PDs); transformers; BREAKDOWN CHARACTERISTICS; WAVE-FORMS; INSULATION; GIS; OIL; STRENGTH; SF6;
D O I
10.1109/TDEI.2022.3205291
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Oscillating lightning impulse (OLI) voltage is recommended for on-site testing due to its high generation efficiency. In this article, partial discharge (PD) characteristics under field impulse voltage waveforms are investigated. The experiment is carried out on a scaled transformer model with a protrusion defect inside as the PD source. Both oscillating and standard lightning impulse (SLI) voltages are acquired as test waveforms. Main discharges and reverse discharges are detected simultaneously under both OLI and SLI voltage. The increasing applied voltage amplitude advances the main discharge and enlarges its amplitude, and it also prolongs the duration of the reverse discharge and increases the number. The amplitude of main discharge is related to the PD voltage, while that of reverse discharge depends on the dynamic variation of the impulse voltage. Since OLI voltage contains multiple rising edges during the oscillation period, more PDs are excited. A disruptive effect (DE) model is extended for the PD analysis to show the oscillation effect on the PD distribution. The OLI test with PD measurement performed on a 220-kV transformer proves that PD detection during impulse voltage withstand test reflects more detailed information that can be used for early diagnosis of power transformers.
引用
收藏
页码:2303 / 2311
页数:9
相关论文
共 50 条
  • [1] Comparison of Partial Discharge Measurement Methods under the Oscillating Lightning Impulse Voltage in GIS
    Liang, Jianfeng
    Zhang, Liang
    Li, Junhao
    Li, Yanming
    [J]. 2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 900 - 903
  • [2] Study on Partial Discharge Characteristics of Corona Discharge in Transformer Oil under Oscillating Switching Impulse Voltage
    Liang, Jianfeng
    Zhang, Liang
    Li, Junhao
    Li, Yanming
    [J]. 2013 IEEE CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA (CEIDP), 2013, : 1173 - 1176
  • [3] Research on Partial Discharge Characteristics of Protrusion defect in GIS Under Oscillating Lightning Impulse Voltage
    Hu, Mengchen
    Han, Xutao
    Li, Qiuyang
    Wang, Shengfu
    Chen, Yao
    Li Junhao
    [J]. 2016 INTERNATIONAL CONFERENCE ON CONDITION MONITORING AND DIAGNOSIS (CMD), 2016, : 920 - 923
  • [4] Partial discharge measurement and analysis under lightning impulse superimposed DC voltage in SF6 gas
    Wang, Haotian
    He, Cong
    Guo, Ruochen
    Meng, Xuan
    Yuan, Wenze
    Li, Junhao
    [J]. HIGH VOLTAGE, 2022, 7 (04) : 744 - 752
  • [5] Oscillating Lightning Impulse Voltage Withstand Test and Partial Discharge Detection Technology for Power Transformers
    Zhang, Xuanrui
    Wang, Haotian
    Hu, Yidan
    Zhou, Yang
    Li, Junhao
    Han, Xutao
    [J]. Gaodianya Jishu/High Voltage Engineering, 2023, 49 (12): : 5032 - 5041
  • [6] Fractal analysis of streamer patterns in transformer oil under lightning impulse voltage
    Ge, Yang
    Du, Qian
    Shan, Bingliang
    Lv, Yuzhen
    Li, Chengrong
    Yuan, Jinsha
    [J]. 2016 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2016,
  • [7] Partial Discharge Detection and Analysis of Needle-Plane Defect in SF6 under Negative Oscillating Lightning Impulse Voltage Based on UHF Method
    Zhang, Liang
    Han, Xutao
    Li, Junhao
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2017, 24 (01) : 296 - 303
  • [8] Partial Discharge Characteristics of Surface Defect in SF6 Under Oscillating Impulse Voltage
    Han, Xutao
    Pang, Peichuan
    Zhang, Liang
    Zhang, Qian
    Li, Junhao
    [J]. 2018 IEEE INTERNATIONAL CONFERENCE ON HIGH VOLTAGE ENGINEERING AND APPLICATION (ICHVE), 2018,
  • [9] Surface Partial Discharge Measurement and Numerical Calculation Under AC and Lightning Impulse Superimposed Voltage in SF6 Gas
    He, Cong
    Zhang, Xuanrui
    Yuan, Wenze
    Guo, Ruochen
    Li, Junhao
    [J]. Zhongguo Dianji Gongcheng Xuebao/Proceedings of the Chinese Society of Electrical Engineering, 2021, 41 (01): : 200 - 210
  • [10] Field test and analysis of partial discharge on GIS under impulse voltage
    Sun, Qiang
    Dong, Ming
    Ren, Zhong
    Ren, Ming
    Li, Yanming
    Qiu, Aici