Flashover dynamic model of polluted insulators under ac voltage

被引:74
|
作者
Dhahbi-Megriche, N [1 ]
Beroual, A [1 ]
机构
[1] Ecole Cent Lyon, Ctr Genie Elect Lyon, Lyon, France
关键词
D O I
10.1109/94.841822
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents a dynamic model allowing the prediction of discharge activity leading to flashover of polluted insulators. It takes into account the instantaneous changes of the discharge (arc) parameters. For a given voltage, geometry and pollution severity, the model enables one to determine the following parameters: temporal evolution of the current, are resistance, propagation velocity, charge injection and flashover time lag. The flashover voltage characteristic as a function of the surface conductivity of insulators calculated by this model is quite satisfactory in contrast to the empirical and semi-empirical models reported in the literature. The leakage currents computed by our model are found to be in a good agreement with those measured in the laboratory.
引用
收藏
页码:283 / 289
页数:7
相关论文
共 50 条
  • [1] Computation of AC flashover voltage of polluted HV insulators using a dynamic arc model
    Gencoglu, M. T.
    Cebeci, M.
    [J]. EUROPEAN TRANSACTIONS ON ELECTRICAL POWER, 2009, 19 (05): : 689 - 701
  • [2] Predictive dynamic model of the leakage current and flashover voltage of discontinuously polluted insulators under ac voltage: experimental validation
    Dhahbi-Megriche, N.
    Beroual, A.
    [J]. JOURNAL OF PHYSICS D-APPLIED PHYSICS, 2007, 40 (24) : 7782 - 7786
  • [3] Dynamic model to predict AC critical flashover voltage of nonuniformly polluted insulators under thermal ionization conditions
    Shahabi, Saeed
    Gholami, Ahmad
    [J]. TURKISH JOURNAL OF ELECTRICAL ENGINEERING AND COMPUTER SCIENCES, 2017, 25 (03) : 2322 - 2335
  • [4] CALCULATION OF DC AND AC FLASHOVER VOLTAGE OF POLLUTED INSULATORS
    GUAN, ZC
    ZHANG, R
    [J]. IEEE TRANSACTIONS ON ELECTRICAL INSULATION, 1990, 25 (04): : 723 - 729
  • [5] Model for Polluted Insulator Flashover under AC or DC Voltage
    Chihani, T.
    Mekhaldi, A.
    Beroual, A.
    Teguar, M.
    Madjoudj, D.
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (02) : 614 - 622
  • [6] Electrical Circuit Flashover Model of Polluted Insulators under AC Voltage Based on the Arc Root Voltage Gradient Criterion
    Yang, Qing
    Wang, Rui
    Sima, Wenxia
    Jiang, Chilong
    Lan, Xing
    Zahn, Markus
    [J]. ENERGIES, 2012, 5 (03): : 752 - 769
  • [7] Dynamic Arc Model of the Flashover of the Polluted Insulators
    Bessedik, S. A.
    Hadi, H.
    [J]. 2011 ANNUAL REPORT CONFERENCE ON ELECTRICAL INSULATION AND DIELECTRIC PHENOMENA, VOLS 1 AND 2, 2011, : 550 - 554
  • [8] AC Flashover Voltage Model for Polluted Suspension Insulators and an Experimental Investigation in Salt Fog
    Dong, Bingbing
    Zhang, Zhu
    Xiang, Nianwen
    Yang, Hejun
    Xu, Shuiqing
    Cheng, Tingli
    [J]. IEEE ACCESS, 2020, 8 : 187411 - 187418
  • [9] POLLUTED INSULATOR FLASHOVER MODEL FOR AC VOLTAGE
    GHOSH, PS
    CHATTERJEE, N
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 1995, 2 (01) : 128 - 136
  • [10] Modeling of altitude effects on AC flashover of polluted high voltage insulators
    Rizk, FAM
    Rezazada, AQ
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1997, 12 (02) : 810 - 822