Simplified Setting Method of Distance Backup Protection Based on Random Matrix Theory

被引:0
|
作者
Zhao, Zihan [1 ]
Yang, Xiangfei [1 ]
Xiang, Bo [1 ]
Chen, Hongjing [1 ]
Tian, Fengxun [2 ]
Yi, Jianbo [2 ]
机构
[1] State Grid Sichuan Elect Power Co, Dispatching Control Ctr, Chengdu, Peoples R China
[2] Univ Elect Sci & Technol China, Lab Widearea Measurement & Control Power Syst Sic, Chengdu, Peoples R China
关键词
backup protection; distance zone-II protection; random matrix theory; spectral analysis;
D O I
暂无
中图分类号
TE [石油、天然气工业]; TK [能源与动力工程];
学科分类号
0807 ; 0820 ;
摘要
The setting of traditional distance zone-II protection is very complicated, which is due to the difficulty in determining the operating mode and its branch coefficient under the cooperation of multiple lines. So this paper proposes a novel simplified setting method of distance backup protection. This method simplifies the calculation of setting value and accelerates the action time of protection device,which makes the distance zone-II protection only cooperate with the protection of zone-I of local line and only consider the sensitivity coefficient. To further ensure the selectivity of relay protection, the paper develops a fault line detection to match the above method based on random matrix spectral analysis, whose matrix formed by the measured lines current. Then the paper designs a feasible simplified setting process of distance zone-II backup protection by integrating the above methods. Finally, the example analysis shows the simplified setting method of distance backup protection can ensure the selectivity of relay protection, correctly identify the faulty line and speed up the action time.
引用
收藏
页码:1457 / 1461
页数:5
相关论文
共 50 条
  • [1] Backup distance protection scheme based on WAMS
    School of Electrical Engineering, Xi'an Jiaotong University, Xi'an
    710049, China
    Dianli Zidonghua Shebei Electr. Power Autom. Equip., 3 (75-80):
  • [2] Phase distance protection setting method based on detecting impedance
    Sichuan University, Chengdu 610065, China
    Dianli Xitong Baohu yu Kongzhi, 2009, 13 (129-133): : 129 - 133
  • [3] Increment factors based online setting for backup protection
    Zhao, Y. (simonchao@zju.edu.cn), 1600, Power System Technology Press (38):
  • [4] Regional backup protection algorithm based on fitting factor of distance protection
    Ma, Jing
    Guo, Yarong
    Wang, Zengping
    Dianli Zidonghua Shebei/Electric Power Automation Equipment, 2015, 35 (08): : 1 - 8
  • [5] An Adaptive Distance Backup Protection Setting Scheme According to the Power Flow Transfer
    Jiang Kai
    Yu Senlin
    Tong Xiaoyang
    Lian Wenchao
    2016 CHINA INTERNATIONAL CONFERENCE ON ELECTRICITY DISTRIBUTION (CICED), 2016,
  • [6] Short distance universality in random matrix theory
    Brezin, E
    NUCLEAR PHYSICS B, 1997, : 1 - 3
  • [7] Pilot protection method of half-wavelength AC transmission lines based on random matrix theory
    Tang, Yutao
    Shu, Hongchun
    He, Kai
    Wang, Guanxue
    Liu, Litao
    Han, Yiming
    Dai, Yue
    ELECTRIC POWER SYSTEMS RESEARCH, 2023, 224
  • [8] A Wide-Area Backup Protection Algorithm Based on Distance Protection Fitting Factor
    Ma, Jing
    Liu, Chang
    Thorp, James S.
    IEEE TRANSACTIONS ON POWER DELIVERY, 2016, 31 (05) : 2196 - 2205
  • [9] A Distance Local Backup Protection Scheme Based on Regional Pilot Principle
    Zhang, Zhiming
    Cong, Wei
    Xiao, Jing
    Feng, Yingchun
    Wang, Anning
    2015 5TH INTERNATIONAL CONFERENCE ON ELECTRIC UTILITY DEREGULATION AND RESTRUCTURING AND POWER TECHNOLOGIES (DRPT 2015), 2015, : 1036 - 1042
  • [10] Sequential method for speech segmentation based on Random Matrix Theory
    Faraji, Neda
    Ahadi, Seyed Mohammad
    Sheikhzadeh, Hamid
    IET SIGNAL PROCESSING, 2013, 7 (07) : 625 - 633