Experimental study on the performance of a heat pump system with refrigerant mixtures' composition change

被引:27
|
作者
Kim, M
Kim, MS
Kim, Y
机构
[1] Seoul Natl Univ, Sch Mech & Aerosp Engn, Seoul 151742, South Korea
[2] Korea Univ, Dept Mech Engn, Seoul 136701, South Korea
关键词
D O I
10.1016/j.energy.2003.12.004
中图分类号
O414.1 [热力学];
学科分类号
摘要
An experimental study on the capacity control of a heat pump system has been performed using refrigerant mixtures of R32/134a. A test apparatus was made of a refrigeration part and two different types of composition changing parts; a single separator system and a separator-rectifier combined system. Analysis of the separation process was made for a basic single separator system. In order to pursue a wider range of composition change, a separator-rectifier combined system with packed-type distillation column was designed with Raschig ring as packing material. The composition changing part was connected to the condenser outlet and the evaporator inlet. Heating capacity, cooling capacity, and coefficient of performance (COP) of the system were measured under heating and cooling conditions. When the single separator system was used as a composition changing part, the range of composition change in the refrigeration system was approximately 13%. Around 26% of composition change was obtained using the separator-rectifier combined system. From the composition change with the separator-rectifier combined system, the capacity improved from 2.6 to 3.4 kW in the cooling test and from 1.8 to 2.4 kW in the heating test. As the composition of R32 increases, heating and cooling capacities were improved, whereas the value of COP with the refrigerant mixture is enhanced due to a temperature glide effect. It is concluded that the system capacity can be adjusted to meet load requirements by controlling the composition of the refrigerant mixture. (C) 2003 Published by Elsevier Ltd.
引用
收藏
页码:1053 / 1068
页数:16
相关论文
共 50 条
  • [1] Combined effect of refrigerant amount reduction and composition change on heat pump system performance during refrigerant mixture leakage
    Jeong, Yeonwoo
    Lee, Sangwook
    Menegazzo, Davide
    Lombardo, Giulia
    Bobbo, Sergio
    Fedele, Laura
    Kim, Min Soo
    APPLIED THERMAL ENGINEERING, 2025, 258
  • [2] Performance Study of Zeotropic Refrigerant Mixtures in an Air Source Heat Pump Water Heater
    Zhang, Chao
    Liu, Ze-Hua
    Tang, Xiao-Wei
    Zhou, Jian
    International Conference on Mechanics, Building Material and Civil Engineering (MBMCE 2015), 2015, : 263 - 268
  • [3] Experimental study on the performance of heat pump drying system
    Zhang, Xukun
    Li, Huadong
    Xu, Gang
    Xiong, Kangming
    Gu, Zhen
    Nongye Gongcheng Xuebao/Transactions of the Chinese Society of Agricultural Engineering, 2006, 22 (04): : 94 - 98
  • [4] Experimental Study on the Performance of a Solar Heat Pump System
    Zhang, Z.
    Lang, Y. L.
    Mehendale, S.
    Zhang, C. Y.
    Chen, Y.
    Tian, J. J.
    JOURNAL OF ENGINEERING THERMOPHYSICS, 2022, 31 (01) : 156 - 172
  • [5] Experimental Study on the Performance of a Solar Heat Pump System
    Z. Zhang
    Y. L. Lang
    S. Mehendale
    C. Y. Zhang
    Y. Chen
    J. J. Tian
    Journal of Engineering Thermophysics, 2022, 31 : 156 - 172
  • [6] Performance analysis of a vapor compression heat pump using zeotropic refrigerant mixtures
    Yilmaz, M
    ENERGY CONVERSION AND MANAGEMENT, 2003, 44 (02) : 267 - 282
  • [7] Experimental study on the effect of refrigerant charging amount on the performance of CO2-air source heat pump system
    Liu, Zeqin
    Zhen, Huiran
    Chang, Yuan
    Han, Kaiyue
    Yu, Yongjie
    Yang, Yang
    Zhao, Taojie
    INTERNATIONAL CONFERENCE ON OPTOELECTRONIC MATERIALS AND DEVICES (ICOMD 2021), 2022, 12164
  • [8] Study on the influence of refrigerant charge on performance of heat pump units
    Zhao Yuqing
    Dai Yun
    Gao Jianling
    Liu Qingqing
    2018 FIRST INTERNATIONAL CONFERENCE ON ENVIRONMENT PREVENTION AND POLLUTION CONTROL TECHNOLOGY (EPPCT 2018), 2018, 199
  • [9] NIST TESTS HEAT-PUMP REFRIGERANT MIXTURES
    不详
    ASHRAE JOURNAL-AMERICAN SOCIETY OF HEATING REFRIGERATING AND AIR-CONDITIONING ENGINEERS, 1992, 34 (07): : 10 - &
  • [10] Improving cold climate air-source heat pump performance with refrigerant mixtures
    Hakkaki-Fard, Ali
    Aidoun, Zine
    Ouzzane, Mohamed
    APPLIED THERMAL ENGINEERING, 2015, 78 : 695 - 703