Sectionalization of Degraded Polymeric Cable with Multiple Joints using TDR Technique

被引:3
|
作者
Kuan, Tze Mei [1 ]
Ariffin, Azrul Mohd [1 ]
Raymond, Wong Jee Keen [2 ]
机构
[1] Univ Tenaga Nas, Coll Engn, Dept Elect & Elect Engn, Kajang, Selangor, Malaysia
[2] Tunku Abdul Rahman Univ Coll, Dept Elect & Elect Engn, Kuala Lumpur, Malaysia
关键词
cable; joint; insulation; reflectometry; TRANSIENTS;
D O I
10.1109/PECon48942.2020.9314302
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
This paper presents the study on time domain reflectometry (TDR) technique in sectionalizing degraded cable along a polymeric insulated cable with multiple joints. TDR has been widely used for fault localization in polymeric cables. However, it only gives an average condition of the cable and could not pinpoint the degraded section along a cable especially for cable with jointing. Hence, this paper investigates the ability of TDR technique to pinpoint degraded cable section for an XLPE cable with two joints. The TDR system is modelled in MATLAB with a 300-metre XLPE cable that is divided into three equal lengths of 100 m and joint together using two cable joints. The location of degraded cable section is varied to study the ability of TDR in detecting degraded cable at various locations. Simulation results are then validated experimentally with the same cable configurations. Findings from validation of results show that TDR is capable of pinpointing the degraded cable section which allow sectionalization to take place for cable replacement.
引用
收藏
页码:245 / 250
页数:6
相关论文
共 50 条
  • [1] Technique for localization of degraded cable insulation regions using TDR measurement artefacts
    Papazyan, Ruslan
    [J]. 2021 13TH ELECTRICAL ENGINEERING FACULTY CONFERENCE (BULEF), 2021,
  • [2] Development of Treeing Detection Method for Cable with Three Insulation Regions Using TDR Technique
    Kuan, Tze Mei
    Ariffin, Azrul Mohd
    [J]. PROCEEDINGS OF THE 2013 IEEE 7TH INTERNATIONAL POWER ENGINEERING AND OPTIMIZATION CONFERENCE (PEOCO2013), 2013, : 172 - 177
  • [3] PRACTICAL CONSIDERATIONS FOR USING A TDR CABLE TESTER
    CASSEL, DK
    KACHANOSKI, RG
    TOPP, GC
    [J]. SOIL TECHNOLOGY, 1994, 7 (02): : 113 - 126
  • [4] INNOVATIVE SIMPLICITY BROUGHT TO POLYMERIC TRANSMISSION CABLE JOINTS
    PARRY, MH
    WILCK, M
    [J]. IEEE TRANSACTIONS ON POWER DELIVERY, 1990, 5 (02) : 760 - 766
  • [5] Quantification of cable deformation using TDR-experiments
    [J]. Karthik, Guntha (gunthakarthik@rocketmail.com), 1600, International Information and Engineering Technology Association (19): : 3 - 4
  • [6] An enhanced TDR and multi-ratio measuring method for locating long-distance distribution cable joints
    Hou, Zhe
    Yang, Bo
    Shi, Chen
    Zhao, Kun
    Teng, Sen
    Yun, Xiahaoyue
    [J]. 2022 IEEE INTERNATIONAL CONFERENCE ON ELECTRICAL ENGINEERING, BIG DATA AND ALGORITHMS (EEBDA), 2022, : 46 - 49
  • [7] Broadband Impedance Spectroscopy For Locating and Detecting Various Type Of Degraded Portion Along with Polymeric Cable
    Siswoyo, Agung
    Zhang, Guan-Jun
    Suwarno
    [J]. 2021 11TH INTERNATIONAL CONFERENCE ON POWER, ENERGY AND ELECTRICAL ENGINEERING (CPEEE 2021), 2021, : 1 - 7
  • [8] Current Integrated Technique for Insulation Diagnosis of Water-tree Degraded Cable
    Wang, Weiwang
    Sonoda, Keita
    Yoshida, Syugo
    Takada, Tatsuo
    Tanaka, Yasuhiro
    Kurihara, Takashi
    [J]. IEEE TRANSACTIONS ON DIELECTRICS AND ELECTRICAL INSULATION, 2018, 25 (01) : 94 - 101
  • [9] Improvement of the TDR/TDT measurement using deconvolution technique in LabView
    Lesnikowski, Jacek
    [J]. PRZEGLAD ELEKTROTECHNICZNY, 2011, 87 (03): : 274 - 276
  • [10] Amelioration of a degraded hardsetting soil using an anionic polymeric conditioner
    Chan, KY
    Sivapragasam, S
    [J]. SOIL TECHNOLOGY, 1996, 9 (1-2): : 91 - 100