Analysis of the uninterruptible power supply influences to the power grid

被引:0
|
作者
Pilat, Nicole [1 ]
Peric, Ante [1 ]
Ban, Zeljko [1 ]
Sunde, Viktor [1 ]
机构
[1] Univ Zagreb, Fac Elect Engn & Comp, Zagreb, Croatia
关键词
Uninterruptible power supplies; power factor correction; power converter;
D O I
10.23919/mipro.2019.8757049
中图分类号
TM [电工技术]; TN [电子技术、通信技术];
学科分类号
0808 ; 0809 ;
摘要
Systems of uninterruptible power supplies (UPS) are indispensable part of many industrial plants, transportation, telecommunications and other systems, enabling their proper functioning and supply with stable DC and AC voltages. The structure of power section of the UPS system typically consists of a DC link and two converters which perform an indirect AC conversion with bidirectional energy flow. This article provides an overview of the various topologies and structures of the advanced UPS system. UPS input rectifier circuits used to achieve power factor correction (PFC) are specifically described in accordance with the requirements to the load powered by the UPS system. In addition to comparative analysis of these circuits, their main advantages and disadvantages are described. The simulation models of the power and control part of the selected solutions are elaborated for program package MATLAB and PLECS as well. In addition, simulation experiments based on developed models are carried out in order to analyze solution functionality, in terms of PFC and UPS influence to power grid.